64 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 3 Programming and Parameters
P039 [Accel Time 1] Related Parameter(s): P038
, P040, T051...T054, A141, A143...A146, A147
Sets the rate of acceleration for all speed increases.
Values Default: 20.00 Secs 2.2-110 kW (3.0-150 HP)
60.00 Secs 132-250 kW (200-350 HP)
Min/Max: 0.00/600.00 Secs
Display: 0.01 Secs
Maximum Freq
Accel Rate
Accel Time
=
Speed
0
Time
P035 [Maximum Freq]
P039 or A147
[Accel Time x]
P040 or A148
[Decel Time x]
0
Acceleratio
n
Deceleration
P040 [Decel Time 1] Related Parameter(s): P038, P039, T051...T054, A141, A143...A146, A148
Sets the rate of deceleration for all speed decreases.
Values Default: 20.00 Secs 2.2-110 kW (3.0-150 HP)
60.00 Secs 132-250 kW (200-350 HP)
Min/Max: 0.00/600.00 Secs
Display: 0.01 Secs
Maximum Freq
Decel Rate
Decel Time
=
Speed
0
Time
P035 [Maximum Freq]
P039 or A147
[Accel Time x]
P040 or A148
[Decel Time x]
0
Acceleration
Deceleration
P041 [Reset to Defalts]
Stop drive before changing this parameter.
Resets all parameter values to factory defaults.
Options 0 “Ready/Idle” (Default)
1 “Factory Rset” After the reset function is complete, this parameter will set itself back to “0.
Causes an F48 Params Defaulted
fault.
IMPORTANT
Drives packaged for fan and pump applications ship with custom default settings that differ from Factory Defaults. Setting this parameter to option 1 will
require reprogramming of select parameters. Refer to publication 22C-IN002
for packaged drive default settings.
P042 [Auto Mode] Related Parameter(s): P036, P038
Stop drive before changing this parameter.
Determines the operation of the Auto” key on the integral keypad. Refer to page 50 for details.
Options 0 “No function” LED above “Auto” key is always dark.
1 “Hnd-Off-Auto” (Default) Toggles control start and frequency to and from keypad; starts drive.
2 “Local/Remote” Toggles control start and frequency to and from keypad.
3 Auto/Manual” Toggles only the frequency control to and from keypad.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 22C-D072A103 and is the answer not in the manual?

Allen-Bradley 22C-D072A103 Specifications

General IconGeneral
BrandAllen-Bradley
Model22C-D072A103
CategoryController
LanguageEnglish

Related product manuals