Rockwell Automation Publication 2711P-IN001J-EN-P - April 2018 11
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
Install the Terminal
Before installing the terminal in a panel, review the following topics:
• Mounting clearances
• Panel cutout dimensions
• Product dimensions
Mounting Clearances
Allow adequate clearance around the terminal, inside the enclosure, for adequate ventilation.
Consider heat produced by other devices in the enclosure. The ambient temperature around the
terminals must be between 0…55 °C (32…131 °F).
These minimum clearances are required for ventilation.
• Top clearance: 51 mm (2 in.)
• Bottom clearance: 102 mm (4 in.)
• Side clearances: 25 mm (1 in.)
• Back clearance: 25 mm (1 in.)
Minimum side clearance for insertion of memory card is 102 mm (4 in.).
Panel Cutout Dimensions
Use the full size template shipped with your terminal to mark the cutout dimensions.
Terminal Type Height, mm (in.) Width, mm (in.)
700 Keypad or Keypad and Touch 167 (6.57) 264 (10.39)
700 Touch 154 (6.08) 220 (8.67)
1000 Keypad or Keypad and Touch 224 (8.8) 375 (14.75)
1000 Touch 224 (8.8) 305 (12.00)
1250 Keypad or Keypad and Touch 257 (10.11) 390 (15.35)
1250 Touch 257 (10.11) 338 (13.29)
1500 Keypad or Keypad and Touch 305 (12.00) 419 (16.50)
1500 Touch 305 (12.00) 391 (15.40)