EasyManuals Logo
Home>Aritech>Fire Alarms>FP2000 Series

Aritech FP2000 Series User Manual

Aritech FP2000 Series
29 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
FP2000 SERIES ANALOGUE ADDRESSABLE FIRE PANEL: USER INSTRUCTIONS Version 3.1
7. ROUTINE MAINTENANCE
In order to ensure the reliable operation of the FP2000 Series systems, they should be
regularly tested and serviced.
The following maintenance routine should be adopted:
7.1 DAILY
On a daily basis the user should check the following:
7.1.1 that the panel indicates normal operation, or if not, that any fault indicated is
recorded in the logbook and reported to the maintenance personnel;
7.1.2 any fault warning recorded the previous day has received attention;
7.1.3 that the printer ribbon and paper supply are adequate (if applicable), or else
replace as shown in Appendix A.
7.2 QUARTERLY
On a quarterly basis the following actions should take place:
7.2.1 logbook entries should be checked and the necessary action taken;
7.2.2 the state of the batteries and corresponding connections should be checked;
7.2.3 the fire panel should be visually inspected for signs of moisture ingress and
other deterioration;
7.2.4 the alarm, fault and ancillary functions of the fire panel should be tested.
May 1997 Product Code: LKFP2403 Document No: 970528/205/M Page 17

Other manuals for Aritech FP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech FP2000 Series and is the answer not in the manual?

Aritech FP2000 Series Specifications

General IconGeneral
BrandAritech
ModelFP2000 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals