Pressure Sensor
to
from
Pa kPa MPa kgf/cm
2
mmHg mmH₂O psi bar inHg
1kPa 1000.000 1 0.001000 0.010197 7.500616 101.9716 0.145038 0.010000 0.2953
1kgf/cm
2
98066.54 98.066543 0.09806 1 735.5595 10000.20 14.22334 0.980665 28.95878
1mmHg 133.322368 0.133322 0.000133 0.001359 1 13.5954 0.019336 0.001333 0.039370
1mmH
₂O 9.80665 0.00980
-
0.000099 0.0735578 1 0.00142 0.000098 0.002895
1psi 6894.757 6.89757 0.00689 0.070307 51.71630 703.07 1 0.068947 2.036003
1bar 100000.0 100.0000 0.100000 1.019689 750.062 10196.89 14.50339 1 29.52998
1inHg 3386.417 3.388418 0.003386 0.034532 25.40022 345.31849 0.491158 0.033863 1
Pressure type
Gauge pressure
Negative pressure Standard pressure Compound pressure
Model
※
1
Voltage output PSAN-(L)V01C(P)V- PSAN-(L)01C(P)V- PSAN-(L)1C(P)V- PSAN-(L)C01C(P)V-
Current output PSAN-(L)V01C(P)A- PSAN-(L)01C(P)A- PSAN-(L)1C(P)A- PSAN-(L)C01C(P)A-
Hold/Auto shift input PSAN-(L)V01C(P)H- PSAN-(L)01C(P)H- PSAN-(L)1C(P)H- PSAN-(L)C01C(P)H-
Rated pressure range 0.0 to -101.3kPa 0.0 to 100.0kPa 0 to 1,000kPa -101.3kPa to 100.0kPa
Display pressure range 5.0 to -101.3kPa -5.0 to 110.0kPa -50 to 1,100kPa -101.3kPa to 110.0kPa
Min.display unit 0.1kPa 0.1kPa 1kPa 0.1kPa
Max. pressure range 2 times of rated pressure 2 times of rated pressure 1.5 times of rated pressure 2 times of rated pressure
Applied vapor • Pneumatic type
-
Air, Non-corrosive gas
Applied fl uid • Fluid type
-
Air, Non-corrosive gas and fluid that will not corrode SUS316L
Power supply 12V-24VDC ±10%(ripple P-P:Max. 10%)
Current consumption Max. 50mA(Analog Current Output type Max 75mA)
Control output
NPN or PNP open collector output
• Load voltage: Max. 30VDC • Load current: Max. 100mA • Residual voltage
-
NPN: Max. 1V, PNP: Max. 2V
Hysteresis
※
2
Min. display range
Repeat error ±0.2%F.S. ± Min. display range
Response time
Selectable 2.5ms, 5ms, 100ms, 500ms, 1000ms
Short circuit protection Built-in
Analog
output
※
3
Voltage output
• Output voltage: 1-5VDC ±2% F.S. • Linear: Within ±1% F.S. • Output impedance: 1kΩ
• Zero point: Max. 1VDC ±2% F.S. • Span: Max. 4VDC ±2% F.S. •
Response time
: 50ms
• Resolution: Automatically changed to 1/1000 or 1/2000 by pressure unit
Current output
• Output current: DC4-20mA ±2% • Linear: Max. ±1% F.S. • Zero-point: Max. DC4mA ±2% F.S.
• Span: Max. DC16mA ±2% F.S. •
Response time
:70ms
• Resolution: Automatically changed to 1/1000 or 1/2000 by pressure unit
Display method 7segment LED Display
Min. Display interval
※
4
Resolution
Pressure unit
1000 2000 1000 2000 1000 2000 1000 2000
MPa
--
0.001
-
0.001
---
kPa 0.1
-
0.1
-
1
--
0.1
kgf/cm
2
0.001
-
0.001
-
0.01
--
0.001
bar 0.001
-
0.001
-
0.01
--
0.001
psi
-
0.01
-
0.01
-
0.1
-
0.02
mmHg
-
0.4
-
0.8
inHg
-
0.02
-
0.03
mmH₂O 0.1
--
0.1
Display accuracy 0℃ to 50℃ : Max. ±0.5% F.S., -10 to 0℃ : Max. ±1% F.S.
Dielectric strength 1000VAC 50/60Hz for 1 minute
Insulation resistance Min. 50MΩ(at 500VDC megger)
Vibration 1.5mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z direction for 2 hours
Environ-
ment
Ambient temperature
-10 to 50
℃
, storage : -20 to 60
℃
Ambient humidity
30 to 80%RH, storage :30 to 80%RH
Protection IP40(IEC specification)
Material
• Pneumatic type - Front case: PC, Rear case: PC, Pressure port: Nickel Plated Brass
• Fluid type - Front case: PC, Rear case: PA6, Pressure port: SUS316L
Cable
Connector cable (ø4, 5-wire, Length: 2m)
(AWG 24, Core diameter : 0.08mm, Number of cores : 40, Insulator out diameter: ø1mm)
Approval
Unit weight • Pneumatic type - Approx. 80g • Fluid type - Approx. 87.5g
Ex) For calculating 760mmHg as kPa : According to above chart, 1mmHg is 0.133322kPa, therefore 760mmHg will be 760×0.133322kPa=101.32472kPa.
※
1: For '(L)', '(P)', '
' of model name, refer to '
Ordering information'.
※
2: In hysteresis output mode, detection difference is variable.
※
3: It is allowed to select one analog output type only.
※
4: Resolution(1000/2000) of min. Display interval is automatically selected depend on pressure units.
※
F.S. : Rated pressure.
※
There may be ±1digit error in hysteresis by pressure unit calculation error.
※
Environment resistance is rated at no freezing or condensation.
Pressure conversion chart