BSD-340-user-guide-eng, Doc. 1004474-2, 2020-09-18,
Autronica Fire and Security AS
Page 12
3.5 Disable loop
From the Autrosafe panel, disable the loop which you are about to upgrade.
3.6 Download software to BSD-340
a. Press Open to the right of "EEProm". Go to the folder where you have stored the new
software files. Select *.EEP file from folder
b. Press Open to the right of "Application". Go to the folder where you have stored the new
software files. Select *.hex file from folder
c. Press Boot to set loop driver in boot loader mode
d. Verify Bootloader loaded (Bootloader BSD340 June 9 2004 10:54:54) in the "output
window" in IFG service tool.
e. Upgrade EEProm by clicking Program on the right-hand side - wait for completed
confirmation in the Command Input window
f. Upgrade hex by clicking Program on the right-hand side - wait for completed confirmation
in the Command Input window
g. Press Run – loop driver will start
h. Type #? followed by Enter in the Command input window to verify correct version Notice
that AFB Switch addr will change according to the set address on the loop driver.
i. If system number noted in step 3.1 (Before you start) is different from 0: Type #SetSysNoX
(X = earlier system number) and enter in the Command input window

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica AutroSafe BSD-340 and is the answer not in the manual?

Autronica AutroSafe BSD-340 Specifications

General IconGeneral
BrandAutronica
ModelAutroSafe BSD-340
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals