Page 5
1.5 Safety
“Memory fault” is a warning meaning that the loop is not running normally. The actual loop must
be checked and verified for correct cabling and content.
1.6 Compatibility
1.6.1 AutroSafe IFG
BSD-340 PowerLoop Driver software version 1.1.0 is only compatible with AutroSafe software
version 4.3.1 or later.
If your installation uses subscription of analog values from BN-342 or HC-300, using AutroSafe
4.8.1 or newer will give the best PowerLoop crosstalk performance. Using older AutroSafe
versions will work correctly, but the PowerLoop data traffic is higher.
1.6.2 Loop units
BSD-340 PowerLoop Driver software version 1.1.0 is only compatible with loop unit software as
listed below:
• BSD-340 Version 1.0.7.0 or later
• BN-342 Version 1.4 or later
• X33 Version 1.5 or later
• HC300 Version 1.2 or later
All loop units delivered since 2009 have the latest software version. The above software versions
are available in:
• PowerloopUpgradeTool_3_8
• IFG_UpgradeTool_3_8
1.7 Tools
• PC with serial port (or USB to serial converter)
• Serial cable male and female 9 pin D-Sub
• IFG Service Tool (PC application - see chapter 7)
• BSD-340 upgrade files (available to download from the Autronica Product Web).