4.10 . Parameter list and breakdown table
4.10.1 Electronic control fault table
Can be judged according to the remote controller failure code and trouble-
shooting
25
Protect/fault Fault dis-
play
Reason Elimination methods
Inlet Temp. Sensor
Fault
P01 The temp. Sensor is
broken or short circuit
Check or change the
temp. Sensor
Outlet Temp. Sen-
sor Fault
P02 The temp. Sensor is
broken or short circuit
Check or change the
temp. Sensor
Amibent Temp.
Sensor Fault
P04 The temp. Sensor is
broken or short circuit
Check or change the
temp. Sensor
Coil 1 Temp. Sen-
sor Fault
P05 The temp. Sensor is
broken or short circuit
Check or change the
temp. Sensor
Coil 2 Temp. Sen-
sor Fault
P15 The temp. Sensor is
broken or short circuit
Check or change the
temp. Sensor
Suction Temp.
Sensor Fault
P07 The temp. Sensor is
broken or short circuit
Check or change the
temp. Sensor
Discharge Temp.
Sensor Fault
P081 The temp. Sensor is
broken or short circuit
Check or change the
temp. Sensor
Exhaust Air over
Temp Prot.
P082 The compressor is
overload
Antifreeze Temp.
Sensor Fault
P09 Antifreeze temp sensor
is broken or short cir-
cuited
check and replace this
temp sensor
Pressure sensor
Fault
PP The pressure Sensor is
broken
Check or change the
pressure Sensor or pre-
ssure
High Pressure Prot. E01 The high-preesure
switch is broken
Check the pressure
switch and cold circuit