14
Assembly and Operating Instructions
Setting the DIP switches
MLS Basic Card
MLS Professional Card
Switch Position Illustration Function
DIP 1
ON
Automatic mode in UP direction
OFF
Dead-man mode in UP direction
Switch Position Illustration Function
DIP 1.1
ON
1 2345678
ON DIP
12
ON
DIP 1 DIP 2
Pneumatic (DW) safety edge connected, DW testing is activated
OFF
1 2345678
ON DIP
12
ON
DIP 1 DIP 2
Electric or FRABA OSE safety edge connected
DIP 1.2
ON
1 2 345678
ON DIP
12
ON
DIP 1 DIP 2
Deactivate at the bottom end limit via switching pulse from the electric,
pneumatic or optoelectronic safety edge
OFF
1 2 345678
ON DIP
12
ON
DIP 1 DIP 2
Deactivate at the bottom end limit via the cam limit switches on the drive
DIP 1.3
ON
123 45678
ON DIP
12
ON
DIP 1 DIP 2
Move up to the top end limit after a safety stop
OFF
123 45678
ON DIP
12
ON
DIP 1 DIP 2
Move clear of the obstacle after a safety stop with a clearance time Z1 = 2 s
DIP 1.4
ON
123 4 5678
ON DIP
12
ON
DIP 1 DIP 2
Relieve the safety edge at the bottom end limit (reversing) with reversing
time Z5 = 100 ms
OFF
123 4 5678
ON DIP
12
ON
DIP 1 DIP 2
No relief (reversing) at the bottom end limit
DIP
1.5/1.6
ON/ON
12345678
ON DIP
12
ON
DIP 1 DIP 2
Relay 1: warning light, early warning
only for automatic closing
Relay 2: yard light
ON/OFF
12345678
ON DIP
12
ON
DIP 1 DIP 2
Relay 1: trafc lights,
door at top end limit
Relay 2: yard light
OFF/ON
12345678
ON DIP
12
ON
DIP 1 DIP 2
Relay 1: warning light,
always with early warning
Relay 2: yard light
OFF/OFF
12345678
ON DIP
12
ON
DIP 1 DIP 2
Relay 1: door status,
door at top end limit
Relay 2: door status,
door at bottom end limit
DIP 1.7
ON
1234567 8
ON DIP
12
ON
DIP 1 DIP 2
Relay 1: warning light ashing,
ash rate 1 Hz
Relay 2: yard light,
control pulse 1 s
OFF
1234567 8
ON DIP
12
ON
DIP 1 DIP 2
Relay 1: warning light
on continuously
Relay 2: yard light, remaining on
for 120 s (time Z6)
DIP 1.8
ON
1234567 8
ON DIP
12
ON
DIP 1 DIP 2
Automatic closing time Z4 is reduced to 3 s after releasing the photoelec-
tric barrier
OFF
1234567 8
ON DIP
12
ON
DIP 1 DIP 2
Automatic closing time (time Z4) re-runs via light barrier function.
DIP 2.1
ON
12345678
ON DIP
1 2
ON
DIP 1 DIP 2
Electric or pneumatic safety edge connected
OFF
12345678
ON DIP
1 2
ON
DIP 1 DIP 2
Optoelectronic safety edge FRABA OSE connected
DIP 2.2
ON
12345678
ON DIP
1 2
ON
DIP 1 DIP 2
Terminating resistance of safety edge = 1.2 kOhm
OFF
12345678
ON DIP
1 2
ON
DIP 1 DIP 2
Terminating resistance of safety edge = 8.2 kOhm