EL34xx284 Version: 1.5
Proceed as follows, unless instructed otherwise by Beckhoff support. Valid for TwinCAT2 and 3 as
EtherCAT master.
Switch TwinCAT system to ConfigMode/FreeRun with cycle time >= 1 ms (default in ConfigMode is 4
ms). A FW-Update during real time operation is not recommended.
Switch EtherCAT Master to PreOP
Switch slave to INIT (A)
Switch slave to BOOTSTRAP
Check the current status (B, C)
Download the new *efw file (wait until it ends). A pass word will not be neccessary usually.
After the download switch to INIT, then PreOP
Switch off the slave briefly (don't pull under voltage!)
Check within CoE 0x100A, if the FW status was correctly overtaken.
8.4.4 FPGA firmware *.rbf
If an FPGA chip deals with the EtherCAT communication an update may be accomplished via an *.rbf file.
Controller firmware for processing I/O signals
FPGA firmware for EtherCAT communication (only for terminals with FPGA)