Resetting the Device to Factory Default
1. Reset the AMC2-4W as described above.
2. Open the upper case of the AMC2-4W as described in
Opening the Case, page 22.
3. Set all six DIL switches of the RS-485 selector to ON as
shown in the figure below.
4. Press the reset button on the the board.
5. Set the DIL switches back in the address state before
resetting.
The AMC2-4W now has the following network configuration:
DHCP = 1
IP = [assigned by DHCP server or “0.0.0.0” if not available]
Subnet mask = [assigned by DHCP server or “0.0.0.0” if not
available]
Password = no password
Figure 5.3: Resetting the AMC2 to delivery state
5.3.2
54 en | Operating
Access Modular
Controller
2016-11 | AMC2-4W | Bosch Sicherheitssysteme