D9412GV2/D7412GV2 | Operation and Installation Guide | 3.0 Overview
.
Bosch Security Systems, Inc. | 7/09 | F01U003641-04 11
Table 3: Compatible Accessories (continued)
3
Model Title UL 864 Fire Intrusion
D1255W Text Keypad (white) X X
D1256 Fire Keypad (Command Center) X
D1257 Fire Alarm Annunciator X
D1260/D1260B
1
Keypads X X
D1640 16.5 VAC 40 VA Transformer X X X
D8004 Transformer Enclosure X X X
D8125 POPEX Module X X X
D8125MUX Multiplex Bus Interface X X X
ISW-D8125CW
2
Commercial Wireless Interface Module X
2
D8125INV
2
Inovonics Wireless Interface Module X
2
D8128D OctoPOPIT Module X X X
D8129 OctoRelay Module X X X
D8130 Release Module X X X
D8132 Battery Charger Module X X
D9127U/T POPIT Module X X X
D9131A Parallel Printer Interface Module X X
D9210B Access Control Interface Module X X X
ZX776Z PIR Motion Sensor [15 m (50 ft)] with POPIT X
ZX794Z PIR Motion Sensor [24 m (80 ft)] with POPIT X
ZX865
PIR/Microwave Motion Sensor [+1.7°C (+35°F)] with POPIT
X
ZX938Z PIR Motion Sensor [18 m (60 ft)] with POPIT X
ZX970
PIR/Microwave Motion Sensor [+1.7°C (+35°F)] with POPIT
1
Version 1.03 or above
2
The ISW-D8125CW and the D8125INV were not investigated by UL. Do not use the ISW-D8125CW or D8125INV in UL Listed
installations.
3
Where the fire alarm transmitter is sharing on-premise communications equipment, the shared equipment must be UL Listed (ITE
or fire protective signaling).
3.3 Features in the D9412GV2 and
D7412GV2
3.3.1 SDI Molex Connector
Use the SDI Molex Connector to connect easily an
SDI device with the SDI bus, without needing to
disconnect wires connected to the SDI terminals.
Possible applications include:
• Connecting a DX4010i to program the control
panel with Remote Programming Software (RPS)
at the premises
• Connecting a keypad to test the control panel.
Do not connect the D5200 Programmer to
the SDI Molex connector.
3.3.2 Tip and Ring Posts
The tip and ring posts allow connecting a phone or
buttset for the purpose of troubleshooting
communications between the control panel and the
central station. This connection allows monitoring of
the dial tone, handshaking tones from the receiver,
and communications signals.
3.3.3 Super Capacitor
The D9412GV2 and D7412GV2 have a capacitor
called Super Cap. This component preserves the
parameters stored in the control panel’s RAM chip
when the lithium battery is replaced. The Super Cap
can retain voltage for up to 30 minutes after the
lithium battery is removed.