12.3.9 P0 Troubleshooting
LED display output: P0
Description: Control board is over-heated
Possible causes:
Poor heat dissipation, causing control board to overheat
Tf sensor failed
Wrong connection on control board of T5&Tf (common cause)
Outdoor motor failed, causing control board to overheat
Table 37
Procedure:
Figure 24
Restart the system
Correct T5 and Tf
connections
Yes
No
Yes
Refer to control board
replacement instructions
Correct/Replace motor
No
Yes
Is there poor heat
dissipation?
Did the outdoor fan
motor fail?
No
Are T5 and Tf
connections at
control board
correct?
Replace Tf sensor
Yes
No
Did the Tf sensor
fail?
Replace the control board
Yes
No
Did the control
board fail?
1) See Section 13.6
2) SeeSection 13.4
3) See Appendix 1