70
|
Bosch IDS 2.0 Service Manual
07.2021 | Bosch Thermotechnology Corp.
Data subject to change
13.7 Indoor Blower Motor
Figure 44
Blower should run any time there is a call for
cooling/heating. Only exception is fan delay
for anti cold air function in heating mode.
24V(AC) depends on SW6-1&2 dipswitch fan
speed settings. High or low speed depends on if
Y1 (low) or Y2 (high) call. Measure between
speed pin and C (brown wire).
Tstat Conection Wire Color
R & C Red & Brown
Y & C Yellow & Brown
Replace the control board
No
Yes
No
Fix the wire connection or
power supply
Replace transformer
Yes
No
Is there 230V(AC)
power supply?
Is there 18-
28V(AC) between
CN33 terminals on
IDU control board?
Yes
Is there 18-
28V(AC) between
R&C terminals on
IDU control board?
Fix low voltage
wiring/replace the
thermostat
No
Yes
28V(AC)between
Y1&C
terminals on IDU control
board?
Replace the control board
No
Yes
Is the LED on the
indoor board ON or
flashing?
Replace motor
Replace the control board
No
Yes
Is there
230V(AC) between
CN39 & black wire connected
to transformer?
Replace the control board
No
Yes
Is there 24V(AC)
between the pins at
CN35 on IDU
control board?
Does blower motor
run properly?
Yes
No service required
No
Restart unit, give system
call for heating/cooling
Is there 18-
CN33
CN35