52
|
Bosch IDS 2.0 Service Manual
07.2021 | Bosch Thermotechnology Corp.
Data subject to change
12.3.11 P2/H5 Troubleshooting
LED display output: P2/H5
Description: Low pressure protection
Possible causes:
Poor heat exchange on coil (cooling mode – indoor coil, heating mode – outdoor coil)
Fan motor failure (cooling mode – indoor fan, heating mode – outdoor fan)
Service valves not open
TXV/EEV/filter drier blocked
Under charged
Table 39
Procedure:
Figure 26
P2 occurs 5 times in
100 minutes
Ye s
Ye s
H5 displayed, hard lockout
No
P2 error code
System hard shut down
Power on unit
Is there still a fault
code displayed?
No
No service required
Is there still low
pressure?
Ye s
Is the system
undercharged?
Ye s
Follow IOM to adjust
refrigerant
No
Did the pressure
transducer fail?
Ye s
Replace PT
No
Restart system
Check for abnormal
pressure
No
1) See Section 13.1
2) See Section 13.2