230 Volt connection
-#
)
Connect the 230 Volt electrical equipment and then the circuit breaker in ac-
cordance with the 230 Volt connection diagram (Figure 9).
!" %
1 Green/yellow protective earth connection and potential equalisation.
Conductor cross section 4 mm². Connect the cables without wire
terminating sleeves to the cage tension spring clamps.
2 13 A circuit breaker Cross cable section: 1.5 mm² All module A.
Connect the cables with wire terminating sleeves directly to the
circuit breaker.
3 For the MES 250-2/4 and MES 400-2/4: 16 A circuit breaker Cross
cable section: 2.5 mm²
For the MES 250-3 and MES 400-3: 30 mA differential circuit
breaker. Cross cable section: 1.5 mm² Note the N!