plug-in
Cod. +030221881 rel. 1.5 - 26/10/10
18
3.3 Setting the main operating parameters
The plug-in series instruments are supplied ready to use. They are in fact programmed in the factory (default settings) to respond to
the more common requirements. The programming is performed by assigning all the parameters the more frequently required
value; the table below lists the parameters and the corresponding default value.
code description type
d
min
d
max
default
unit of
measure
(**)
/C
ambient probe calibration
F
-127 127
0
°C/°F x 0,1
/2
measurement stability (probe delay and range limit), 1 = fast
C
1 15
4
/4
selection of probe to display (0 = ambient, 1 = defrost)
C
0 1
0
/5
selection °C/°F (0=°C)
C
0 1
0
rd
control differential (hysteresis)
F
0 19
2
°C/°F
r1
minimum set allowed to the user
C
-50 127
-50
°C/°F
r2
maximum set allowed to the user
C
-50 127
60
°C/°F
r3 enable alarm Ed (1=enable) C
0 1
0
r4
set automatic variation of the Set point for night operation
C
-20 20
3
°C/°F
rL
Direct/Reverse operating mode (note: only valid for models S*A) C 0 1 flag 0
c0
compressor start delay at instrument on
C
0 15
0
min
c1
minimum time between 2 successive starts of the compressor
C
0 15
0
min
c2
minimum compressor off time
C
0 15
0
min
c3
minimum compressor on time
C
0 15
0
min
c4
Duty Cycle safety relay ON time
C
0 100
0
min
cc
continuous cycle duration
C
0 15
4
hours
c6
alarm bypass time after continuous cycle
C
0 15
2
hours
d0
type of defrost (0=heat el., 1=gas, 2=heat. el. time, 3=gas time)
C
0 3
0
dI
interval between two defrosts
F
0 199
8
hours/min
dt
end defrost temperature
F
-50 127
4
°C/°F
dP maximum defrost duration or effective duration for d0=2 or
d0=3
F
1 199
30
min/s
d4
defrosting at instrument on (1=yes)
C
0 1
0
d5
defrost delay
C
0 199
0
min
d6
display off during defrost (1=yes)
C
0 1
1
dd
post-defrost dripping time
F
0 15
2
min
d8
alarm bypass time after defrosting
F
0 15
1
hours
d9
defrost priority over minimum compressor times (1=yes)
C
0 1
0
dC
time basis (0 =hours/min, 1=min/s)
C
0 1
0
A0
alarm/fan differential
C
0 19
0
°C/°F
AL
shift low temperature alarm threshold
F
0 127
0
°C/°F
AH
shift high temperature alarm threshold
F
0 127
0
°C/°F
Ad
temperature alarm delay
C
0 199
0
min
A4
digital input configuration
C
0 4
0
A7
alarm input detection delay
C
0 199
0
min
F0
fan operating mode
C
0 1
1
F1
fan on temperature
F
-50 127
5
°C/°F
F2
fans off with compressor off (1=yes)
C
0 1
1
F3
fans off during defrost (1=yes)
C
0 1
1
Fd
fan time-out during post dripping
F
0 15
1
min
H0
serial address
C
0 199
1
H1
PJ32S: enable defrosting, PJ32C: multifunction relay function
C
0 1
1
H2
disable keypad, 0=disabled
C
0 1
1
H4
disable buzzer
C
0 1
0
L1
control set point
S
-50 127
4
°C/°F
Tab. 3.3.1
(**) unit of measure (hereafter u. of m. in the tables).
To achieve the maximum performance from the controls, or in the case of special needs, the values of the operating parameters can
be modified. The following notes describe the factory settings and the parameters which are more frequently modified (set point,
differential, etc.). Furthermore, for convenience, all parameters which should be checked before operating the unit are indicated.