10
PERFORMANCE DATA
COOLING CAPACITIES
38MVC(Q)009--1 / 40MVC(Q)009--1
Te m p _F(_C)
Air Entering
Condenser
(Edb)
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
190/0.04 259/0.04 327/0.05
Air Entering Evaporator --- Ewb _F(_C)
57
(13.89)
62
(16.67)
67
(19.44)
72
(22.22)
57
(13.89)
62
(16.67)
67
(19.44)
72
(22.22)
57
(13.89)
62
(16.67)
67
(19.44)
72
(22.22)
55
(12.78)
TCG 7.70 8.60 9.37 10.14 9.08 9.34 10.07 10.66 9.75 9.74 10.44 10.93
SHG 7.44 6.61 5.80 4.95 9.08 7.59 6.45 5.29 9.75 8.30 6.95 5.50
TC 7.69 8.58 9.36 10.12 9.07 9.32 10.06 10.65 9.74 9.72 10.42 10.92
kW 0.48 0.48 0.48 0.47 0.48 0.48 0.47 0.47 0.48 0.48 0.47 0.47
CMP 0.39 0.39 0.39 0.38 0.39 0.39 0.38 0.38 0.39 0.39 0.38 0.38
LDB 45.0 48.9 52.8 56.9 48.4 53.5 57.6 61.7 52.9 56.9 60.7 64.8
LWB 40.9 45.6 50.8 56.2 43.3 49.2 54.5 60.2 45.4 51.6 56.9 62.6
65
(18.33)
TCG 7.40 8.31 9.14 9.95 8.88 9.08 9.87 10.51 9.53 9.50 10.27 10.81
SHG 7.40 6.57 5.71 4.88 8.88 7.55 6.41 5.25 9.53 8.34 6.98 5.51
TC 7.38 8.29 9.13 9.93 8.86 9.07 9.85 10.50 9.52 9.48 10.26 10.80
kW 0.54 0.55 0.55 0.54 0.55 0.55 0.54 0.54 0.55 0.55 0.54 0.54
CMP 0.45 0.45 0.46 0.45 0.46 0.46 0.45 0.45 0.45 0.45 0.45 0.45
LDB 45.1 49.1 53.2 57.2 49.1 53.6 57.7 61.9 53.5 56.7 60.6 64.8
LWB 41.6 46.2 51.2 56.5 43.6 49.6 54.8 60.3 45.7 51.9 57.1 62.7
75
(23.89)
TCG 7.50 7.94 8.88 9.73 8.56 8.72 9.57 10.33 9.28 9.12 10.00 10.61
SHG 7.50 6.52 5.62 4.80 8.56 7.49 6.33 5.21 9.28 8.24 6.93 5.50
TC 7.49 7.93 8.87 9.71 8.54 8.70 9.55 10.31 9.26 9.10 9.98 10.60
kW 0.61 0.61 0.62 0.62 0.62 0.62 0.62 0.62 0.62 0.62 0.62 0.62
CMP 0.52 0.52 0.53 0.52 0.52 0.53 0.53 0.52 0.53 0.53 0.52 0.52
LDB 44.7 49.2 53.6 57.6 50.1 53.8 57.9 62.0 54.2 57.0 60.7 64.8
LWB 41.4 47.0 51.7 56.9 44.1 50.1 55.2 60.6 46.0 52.3 57.4 62.8
85
(29.44)
TCG 7.20 7.55 8.50 9.42 8.20 8.09 9.25 10.04 8.99 8.72 9.62 10.34
SHG 7.20 6.49 5.52 4.67 8.20 7.34 6.28 5.12 8.99 8.23 6.86 5.44
TC 7.18 7.53 8.48 9.41 8.19 8.07 9.23 10.03 8.97 8.71 9.61 10.33
kW 0.68 0.69 0.69 0.70 0.69 0.69 0.70 0.70 0.70 0.70 0.70 0.70
CMP 0.59 0.59 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60
LDB 46.0 49.3 54.0 58.2 51.3 54.3 58.1 62.3 54.9 57.0 60.9 65.0
LWB 42.1 47.8 52.5 57.5 44.7 51.1 55.6 60.9 46.4 52.7 57.8 63.1
95
(35)
TCG 6.86 7.02 8.06 9.06 7.82 7.63 8.86 9.66 8.57 8.22 9.22 9.98
SHG 6.86 6.37 5.42 4.53 7.82 7.28 6.20 5.00 8.57 8.22 6.83 5.35
TC 6.85 7.00 8.05 9.05 7.80 7.61 8.85 9.64 8.55 8.20 9.21 9.97
kW 0.76 0.76 0.77 0.78 0.77 0.77 0.78 0.78 0.78 0.78 0.78 0.78
CMP 0.66 0.67 0.68 0.69 0.67 0.67 0.68 0.69 0.68 0.68 0.69 0.69
LDB 47.5 49.8 54.4 58.8 52.6 54.4 58.3 62.7 56.0 57.0 60.9 65.2
LWB 42.8 48.9 53.3 58.1 45.3 51.7 56.2 61.4 46.9 53.3 58.2 63.4
105
(40.56)
TCG 6.40 6.54 7.59 8.70 7.39 7.09 8.26 9.20 8.10 8.10 8.73 9.56
SHG 6.40 6.19 5.28 4.40 7.39 7.09 6.11 4.86 8.10 8.10 6.74 5.26
TC 6.39 6.53 7.58 8.69 7.38 7.07 8.25 9.19 8.08 8.09 8.72 9.54
kW 0.84 0.85 0.86 0.87 0.86 0.85 0.87 0.87 0.86 0.86 0.87 0.87
CMP 0.75 0.75 0.76 0.77 0.76 0.76 0.77 0.77 0.77 0.77 0.77 0.78
LDB 49.6 50.6 55.0 59.4 54.0 55.0 58.6 63.1 57.3 57.3 61.2 65.4
LWB 43.9 49.9 54.2 58.7 46.0 52.5 57.0 61.9 47.5 53.4 58.7 63.8
115
(46.11)
TCG 5.87 5.81 7.03 8.09 6.91 6.91 7.64 8.67 7.59 7.59 8.01 8.99
SHG 5.87 5.79 5.08 4.18 6.91 6.91 5.97 4.70 7.59 7.59 6.61 5.10
TC 5.85 5.80 7.01 8.08 6.89 6.90 7.63 8.65 7.57 7.57 7.99 8.97
kW 0.93 0.93 0.95 0.96 0.95 0.95 0.96 0.97 0.96 0.96 0.96 0.97
CMP 0.83 0.83 0.85 0.86 0.85 0.85 0.86 0.87 0.86 0.86 0.86 0.87
LDB 52.0 52.4 55.9 60.3 55.6 55.6 59.0 63.6 58.7 58.7 61.5 65.8
LWB 45.0 51.3 55.2 59.7 46.7 52.8 57.8 62.5 48.1 54.0 59.4 64.3
125
(51.67)
TCG 5.33 5.33 6.22 7.44 6.37 6.37 6.80 8.09 7.03 7.03 7.00 8.35
SHG 5.33 5.33 4.75 3.96 6.37 6.37 5.71 4.54 7.03 7.03 6.31 4.96
TC 5.31 5.31 6.21 7.42 6.35 6.35 6.78 8.07 7.02 7.02 6.99 8.33
kW 1.03 1.03 1.04 1.06 1.04 1.04 1.05 1.07 1.05 1.05 1.05 1.07
CMP 0.93 0.93 0.94 0.96 0.94 0.94 0.95 0.97 0.95 0.95 0.95 0.97
LDB 54.4 54.5 57.3 61.3 57.5 57.5 59.8 64.1 60.2 60.2 62.2 66.2
LWB 46.2 52.3 56.7 60.8 47.6 53.5 58.8 63.2 48.8 54.6 60.4 64.9
LEGEND
BF --- Bypass Factor
CMP --- Compressor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
k W --- To t a l Po w e r
LDB --- Leaving D ry Bulb
L W B --- L e a v i n g We t B u l b
SHG --- Gross Sensible Capacity (1000 Btu/hour)
TC --- Total Net Cooling Capacity (1000 Btu/hour)
---
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from
SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
38/40MVC, MVQ