22
AIR THROW DATA
UNIT
CAPACITY
APPROXIMATE AIR THROW ft. (m)
Low Medium High
009 115v 14 (4.3 m) 18 (5.5) 28 (8.5)
012 115v 16 (4.9) 20 ( 6.1) 30 (9.1)
012 208/230v 16 (4.9) 20 (6.1) 30 (9.1)
018 208/230v 22 (6.7) 37 (8.2) 35 (10.7)
024 208/230v 23 (7.0) 31 (9.4) 40 (12.2)
SOUND RATINGS
Outdoor Units
Model Number Sound Power dBa Sound Pressure dBa
3 8 M V C 0 0 9 --- --- --- 1 65 54
3 8 M V C 0 1 2 --- --- --- 1 65 54
3 8 M V C 0 1 2 --- --- --- 3 65 54
3 8 M V C 0 1 8 --- --- --- 3 68 57
3 8 M V C 0 2 4 --- --- --- 3 67 56
3 8 M V Q0 0 9 --- --- --- 1 64/66 (Clg/Htg) 53/55 (Clg/Htg)
3 8 M V Q0 1 2 --- --- --- 1 63/64 (Clg/Htg) 52/53 (Clg/Htg)
3 8 M V Q0 1 2 --- --- --- 3 63/64 (Clg/Htg) 52/53 (Clg/Htg)
3 8 M V Q0 1 8 --- --- --- 3 68/72 (Clg/Htg) 57/61 (Clg/Htg)
3 8 M V Q0 2 4 --- --- --- 3 65/67 (Clg/Htg) 54/56 (Clg/Htg)
Indoor Units
Model Number
High Medium Low
Sound Power
dBa
Sound Pressure
dBa
Sound Power
dBa
Sound Pressure
dBa
Sound Power
dBa
Sound Pressure
dBa
4 0 M V C 0 0 9 --- --- --- 1 53 42 47 36 39 28
4 0 M V C 0 1 2 --- --- --- 1 58 47 53 42 51 40
4 0 M V C 0 1 2 --- --- --- 3 58 47 53 42 51 40
4 0 M V C 0 1 8 --- --- --- 3 59 48 56 45 54 43
4 0 M V C 0 2 4 --- --- --- 3 64 53 61 50 59 48
4 0 M V Q0 0 9 --- --- --- 1 52/54 (Clg/Htg) 41/43 (Clg/Htg) 47/47 (Clg/Htg) 36/36 (Clg/Htg) 42/44 (Clg/Htg) 31/33 (Clg/Htg)
4 0 M V Q0 1 2 --- --- --- 1 59/58 (Clg/Htg) 48/47 (Clg/Htg) 54/51 (Clg/Htg) 43/40 (Clg/Htg) 51/47 (Clg/Htg) 40/36 (Clg/Htg)
4 0 M V Q0 1 2 --- --- --- 3 59/58 (Clg/Htg) 48/47 (Clg/Htg) 54/51 (Clg/Htg) 43/40 (Clg/Htg) 51/47 (Clg/Htg) 40/36 (Clg/Htg)
4 0 M V Q0 1 8 --- --- --- 3 58/57 (Clg/Htg) 47/46 (Clg/Htg) 56/56 (Clg/Htg) 45/45 (Clg/Htg) 54/54 (Clg/Htg) 43/43 (Clg/Htg)
4 0 M V Q0 2 4 --- --- --- 3 65/66 (Clg/Htg) 54/55 (Clg/Htg) 62/64 (Clg/Htg) 51/53 (Clg/Htg) 59/60 (Clg/Htg) 48/49 (Clg/Htg)
NOTES:
1. Sound power ratings are per ARI 270 and ARI 350
2. Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.
ELECTRICAL DATA
UNIT
SIZE
OPERATING
VOLT AGE*
COMPRESSOR OUTDOOR FAN INDOOR FAN
MCA
MAX
FUSE/CB
AMP
MAX/MIN V O L T S --- P H --- H Z RLA LRA FLA HP W VOLTS FLA HP W
009
127/104 1 1 5 --- 1 --- 6 0
7.5 40
0.60 0.102 23 35 DC
1.1 0.034 20 12 20
012 9.9 47 1.18 0.044 25 15 25
012
253/187 208/230---1---60
5.2 21 0.38 0.116 36 35 DC 1.18 0.044 25 9 15
018 7.3 32.6 0.78 0.224 53
208/230---1---6.
0.26 0.075 31 11 20
024 9.7 34.8 0.62 0.218 100 0.39 0.112 50 14 25
*Permissible limits of the voltage range at which the unit will operate satisfactorily
LEGEND
FLA --- Fu l l L o a d A m p s
LRA --- L o c k e d R o t o r A m ps
MCA --- Minimum Circuit Amps
RLA --- RatedLoadAmps
38/40MVC, M VQ