PERFORMANCE DATA (CONT.)
INSTANTANEOUS AND INTEGRATED HEATING RATINGS
38MVQ018--3 / 40MVQ018--3
Air Temperature
Entering Indoor
Unit _F(_C)
Indoor
Airflow
(CFM)
L --- M --- H
Item
Air Temperature Entering Outdoor Coil --- DB/WB _F(_C)
57/53 (13.89/11.67) 47/43 (8.33/6.11) 37/33 (2.78/0.56) 27/23 (---2.78/---5) 17/13 (---8.33/---10.56)
Instant. Integrated Instant. Integrated Instant. Integrated Instant. Integrated Instant. Integrated
Rating Rating Rating Rating Rating Rating Rating Rating Rating Rating
55 (12.78)
426
Cap 18.57 18.57 16.44 16.44 0.00 0.00 11.47 10.19 9.32 8.50
kW 1.48 1.38 0.00 1.17 1.20
449
Cap 18.69 18.69 16.53 16.53 14.04 12.77 11.57 10.27 9.39 8.56
kW 1.46 1.36 1.25 1.16 1.19
539
Cap 18.99 18.99 16.76 16.76 14.59 13.28 11.90 10.57 9.62 8.77
kW 1.37 1.29 1.22 1.12 1.16
60 (15.56)
426
Cap 18.23 18.23 16.12 16.12 13.48 12.27 11.10 9.86 8.97 8.18
kW 1.55 1.44 1.31 1.22 1.24
449
Cap 18.34 18.34 16.23 16.23 13.61 12.39 11.19 9.94 9.04 8.25
kW 1.52 1.42 1.30 1.21 1.23
539
Cap 18.66 18.66 16.49 16.49 14.03 12.77 11.49 10.20 9.26 8.45
kW 1.44 1.35 1.26 1.17 1.20
65 (18.33)
426
Cap 17.87 17.87 15.60 15.60 13.05 11.87 10.71 9.51 8.61 7.85
kW 1.62 1.49 1.36 1.26 1.29
449
Cap 18.00 18.00 15.88 15.88 13.18 11.99 10.81 9.60 8.68 7.92
kW 1.59 1.48 1.35 1.25 1.28
539
Cap 18.32 18.32 16.19 16.19 13.59 12.37 11.10 9.86 8.90 8.11
kW 1.50 1.41 1.30 1.22 1.25
70 (21.11)
426
Cap 17.53 17.53 15.09 15.09 12.60 11.46 10.32 9.16 8.26 7.53
kW 1.68 1.54 1.41 1.31 1.33
449
Cap 17.65 17.65 15.26 15.26 12.73 11.59 10.41 9.25 8.32 7.58
kW 1.66 1.52 1.40 1.30 1.32
539
Cap 17.98 17.98 15.88 15.88 13.16 11.98 10.71 9.51 8.52 7.77
kW 1.57 1.47 1.35 1.27 1.30
75 (23.89)
426
Cap 17.17 8.66 14.66 14.66 12.15 8.66 9.92 8.81 7.86 7.17
kW 1.75 1.59 1.46 1.36 1.50
449
Cap 17.29 8.89 14.79 14.79 12.27 8.89 10.01 8.89 7.93 7.24
kW 1.72 1.57 1.45 1.35 1.37
539
Cap 17.64 17.64 15.30 15.30 12.69 11.54 10.30 9.14 8.16 7.44
kW 1.64 1.52 1.40 1.31 1.35
80 (26.67)
426
Cap 16.75 16.75 14.19 14.19 11.72 10.67 9.51 8.45 7.46 6.80
kW 1.81 1.65 1.51 1.41 1.43
449
Cap 16.92 16.92 14.35 14.35 11.84 10.77 9.60 8.53 7.53 6.86
kW 1.79 1.63 1.50 1.40 1.42
539
Cap 17.28 17.28 14.82 14.82 12.22 11.12 9.88 8.78 7.73 1.54
kW 1.71 1.57 1.46 1.36 1.40
Indicates Rating Condition (* Integrated Capacity)
Indicates Integrated Rating
Cap --- Heating Capacity (100 Btuh), Includes indoor f an motor heat
kW --- Total Power Input, includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input
Note: Integrated Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
38/40MVC, MVQ