39
UNIT
Preliminary information
Job name: ..............................................................................................................................................................................................
Location: ................................................................................................................................................................................................
Installing contractor: ............................................................................................................................................................................
Distributor: ...........................................................................................................................................................................................
Equipement
Model 30XAV-ZE: ................................................................................................................................................................................
Compressors
Circuit A Circuit B
Model # Model #
S/N S/N
Motor # Motor #
Inverter compressor frequency Fan Inverter frequency
Model # (circuit A/B) : Model # (circuit A/B) :
Serial number (circuit A/B) : Serial number (circuit A/B) :
Evaporator
Model : ...................................................................................................................................................................................................
S/N ..........................................................................................................................................................................................................
Condensing module
Model # : ................................................................................................................................................................................................
Unit options and additional accessories
.................................................................................................................................................................................................................
.................................................................................................................................................................................................................
Is there any shipping damage ..............................................................................................................................................................
If so, where? ...........................................................................................................................................................................................
Will this damage prevent unit start-up? .............................................................................................................................................
□ Unit is level in its installation
□ Power supply agrees with the unit name plate
□ Electrical circuit wiring has been sized and installed properly
□ Unit ground wire has been connected
□ Electrical circuit protection has been sized and installed properly
□ All terminals are tight
□ All cables and thermistors have been inspected for crossed wires
□ Chilled water pipes are properly connected
□ All plug assemblies are tight
□ The chilled water pump operating with the correct rotation. Check the phase sequence of the electrical connection.
In the case of a unit with hydronic module, use the pump test function (refer to manual control 30XAV-ZE for a
more detailed explanation).
The machine is reset once power off the pump test performed.
□ Circulating ice water in the hydraulic circuit for at least 2 hours, then remove, clean and replace the strainer. The
machine is reset once power off the pump test performed.
□ Piping water inlet to the evaporator includes a strainer with a mesh size of 1.2 mm (20 mesh)