Electric Shock Hazard: This fan tray has to be serviced by trained personnel only.
Caution
This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the absence
of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician
if you are uncertain that suitable grounding is available. Statement 1024
Warning
Use copper conductors only. Statement 1025
Warning
When installing the unit, the ground connection must always be made first and disconnected last. Statement
42
Warning
This unit is to be installed in a restrictive access location and must be permanently grounded to a minimum
6-AWG copper ground wire.
Perform the following procedure to ground the router using a 2-hole lug and the corresponding mounting
point. Most carriers require a minimum 6-AWG ground connection. Verify your carrier’s requirements for
the ground connection.
Procedure
Step 1 If your ground wire is insulated, use a wire-stripping tool to strip the ground wire to 0.5 inch ± 0.02 inch (12.7
mm ±0.5 mm).
Figure 15: Stripping a Ground Wire
Step 2 Slide the open end of your 2-hole ground lug over the exposed area of the ground wire.
Step 3 Using a crimping tool (as specified by the ground lug manufacturer), crimp the ground lug to the ground wire
as shown in the following figure.