Binary inputs – list
Rem Start/Stop
External request for engine run. AUT mode only.
NOTE:
If the binary input Rem Start/Stop is active and mains failure occures, the MCB breaker opens, and
after AMF Settings: Trans Del delay the GCB breaker is closed. Once the mains is OK, the AMF
Settings: MainsReturnDel delay elaspes and the GCB breaker is opened. Then after AMF Settings:
Trans Del delay is MCB breaker closed. Gen-set remains running as long as Rem Start/Stop is active.
See AMF time chart for more details.
Rem Transfer
External request for an immediate transfer from mains to generator without waiting for the AMF
m will stay in
ion of the MODE
e lowest priority.
se of running
her the gen-set is ready to undertake load. Conditions for successful gen-set start and
tpoint – evaluated
rom the state of GenReadyToLoad input. The
o be fulfilled during time defined by AMF Settings: Max Start Del setpoint (which can
input switches a three position ATS switch to its neutral position – it activates the
MCB and GCB off.
ack
MCB Feedback
This input indicates whether MCB is closed or opened.
MainsHealthy
This iinp s creted mainly for cascading applications, where slave controllers do not have usually
Mains and Gen-set voltage measuring inputs connected to the repspective power sources.Then this
binary input tells the controller if Mains is healthy to be able to respond to Mains failure.
Settings: EmergStart Del has elapsed. In the case the transfer not succeeded the syste
neutral position. The MainsFailBlock input performs its work normally.
Remote AUT
If the input is active, AUTO mode is forced to the controller independently on the posit
selector. If another of remote inputs is active, then the REMOTE AUT input has th
MainsFailBlock
If the input is closed, the automatic start of the gen-set at Mains failure is blocked. In ca
gen-set the GCB is opened, gen-set goes to Cooling procedure and stops.
GenReadyToLoad
Indicates wet
readiness to undertake load can be – depending on AMF Settings: GenerProtect se
from the voltage and the frequency of the generator or f
conditions have t
be even unlimited). More info can be found in the setpoint description.
Neutral Pos
In MAN mode this
binary output NeutralPosition and switches the
GCB Feedb
Use this input for indication, whether the generator circuit breaker is open or closed.
If the feedback is not used, connect this input to the output GCB CLOSE/OPEN
ut wa

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliATS NT STD and is the answer not in the manual?

ComAp InteliATS NT STD Specifications

General IconGeneral
BrandComAp
ModelInteliATS NT STD
CategoryController
LanguageEnglish

Related product manuals