InteliATS
NT
STD, SW version 2.0, ©ComAp – June 2010 7
IA-NT- STD-2.0-Reference Guide.pdf
n Descriptio
Description of the controller system
InteliATS
NT
is a comprehensive Automatic Transfer Switch controller designed to mon
AC mains supply (1 or 3 phases) for under & over voltage, under & over frequency an
unbalance. In the case of any mains supply disproportion it will send a remote start co
gen-set and make change over for both
itor the incoming
d voltage
mmand to the
generator and mains contactors. The gen-set requires a
ast a key-start box
over
Controllers
ad transfer between both power sources with break (blackout). Delayed Transition means
used as a switching
r MAINS-GEN
he system recognizes application type according to the Gen Start/Stop and Gen
d (default
ured, MAINS-
n type takes place. In this case stop-fail protection and generator current protection
ay showing icons, symbols and bar-
ionality, new standards in Gen-set
Easy-to-use operation and installation. Factory default configuration covers most of
applications
Different customer changes are possible thanks to the configurability
Excellent remote communication capabilities
High reliability
remote start type control unit (e.g. the ComAp InteliLite
NT
MRS 10 controller), at le
with an external input for the start/stop signal.
The controller uses Open Delayed Transition. This transition is a standard type of change
provided by the most common AMF or ATS controllers supplied by the other vendors.
perform lo
there is a delay between the source breaker opening and the target breaker closing.
Two or three position ATS switch or two independent breakers/contactors can be
mechanism.
InteliATS
NT
controller can be used also for MAINS-MAINS applications and not only fo
applications. T
ReadyToLoad logical binary output and input configuration. If both are configured/use
setting) it tells controller that MAINS-GEN application type is to be used. If not config
MAINS applicatio
a nre ot evaluated.
n eliATS
NT
I t controllers are equipped with a powerful graphic displ
graphs for intuitive operation, which sets, together with high funct
controls.
The key features are:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliATS NT STD and is the answer not in the manual?

ComAp InteliATS NT STD Specifications

General IconGeneral
BrandComAp
ModelInteliATS NT STD
CategoryController
LanguageEnglish

Related product manuals