InteliATS
NT
STD, SW version 2.0, ©ComAp – June 2010 50
IA-NT- STD-2.0-Reference Guide.pdf
ging Remote Control and Data Log
Direct connection to the PC
InteliATS
NT
can be connected directly with PC via optional IL-NT RS232 interface.
Use the standard serial cable to connect PC with InteliATS
NT
.
NOTE:
Make sure the grounding system on controller and PC – COM port (negative of the PC DC supply) are
identical – before the first direct connection. There must not be any voltage between these two points
otherwise the internal reversible fuse in controller burns out. The simple solution is to assure, that the
PC supply 240/20V is ground free (GND terminal is not connected).
5 - GND
2 - RxD
3 - TxD
PC
5 - GND
2 - RxD
3 - TxD
RS232
RS232
230 VAC
0 VDC
CONTROLLER
+
-
Battery
Required the same
voltage potential
between GND‘s
RS 232
PC software – LiteEdit
On the PC (fo n) has to be installed the ComAp’s software package
LiteEd rm)
LiteEdit enabl
control the engine
configure the controller
select software configuration
modify alarm inputs and outputs
modify password, commands protections
direct, modem or Internet communication
r direct or modem connectio
it. (based on Windows 95 or newer platfo
es:
read the quantities
adjust all set points

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliATS NT STD and is the answer not in the manual?

ComAp InteliATS NT STD Specifications

General IconGeneral
BrandComAp
ModelInteliATS NT STD
CategoryController
LanguageEnglish

Related product manuals