InteliATS
NT
STD, SW version 2.0, ©ComAp – June 2010 42
IA-NT- STD-2.0-Reference Guide.pdf
shor eedback
of t se/Open
G ansfer Del
100 must be set to sum of “MCB opening” + “del
after the MCB feedback input deactivates. time.
V [V]
hree is used.
: – 300V
[V]
hree is used.
hold f ll three phases are checked. Maximum out of three is used.
ency
Main <Freq
Threshold for mains underfrequency. All three phases are checked. Maximum out of three is used.
ens On [MAINSFAIL / GENRUN]
If the Transfer Del setpoint is set ter If some delay between MCB f
than the time required for opening he deactivation and closing o f GCB Clo
circuit breaker, the controller closes CB output is required, then the Tr
Close/Open output straight away ( ms)
MCB
Close/Open
MCB
Feedback
GCB
Close/Open
MCB opening del
Transfer Del
M
CB
lose/Open
MCB
Feedback
GCB
Close/Open
C
Mains >
Threshold for mains overvoltage. All three phases are checked. Maximum out of t
V Step: 1
Range (Mains <V)
Mains <V
Threshold for mains undervoltage. All three phases are checked. Maximum out of t
Step: 1V
Range: 50V - (Mains >V)
Mains >Freq [%]
Thr s or mains overfrequency. e A
Step: 0.1% of Nominal frequ
Range: 50 ( s ) – 150.0%
Mains <Freq [%]
Step: 0.1% of Nominal frequency
Range: 50% – 150.0(Mains >Freq)%
MCB Op
MAINSFAIL
ed.
GENRUN
The command to open the MCB is given immediately after mains fail condition evaluat
The command to open the MCB is not given till the Gen-set starts (with respecting the setpoint
EmergStart Del), reaches Running state, reaches proper voltage and frequency and Min Stab Time
elapses. After that, the MCB is opened, Transfer Del timer is started and the GCB is closed after the
timer elapses.
NOTE:
This option should be used for MCBs using 230V control and not equipped with the undervoltage coil.
Transfer
Del
MCB opening

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliATS NT STD and is the answer not in the manual?

ComAp InteliATS NT STD Specifications

General IconGeneral
BrandComAp
ModelInteliATS NT STD
CategoryController
LanguageEnglish

Related product manuals