ESIE16-02B | Part 2. Troubleshooting 2.2. Error based troubleshooting
4/04/17 | Version 1.1 Page 41
RA R32 Split & multi split M-Series
More info:
2.2.3.6. “UF-00” – Wiring and piping mismatch
More info:
2.2.4. Others
Not applicable.
Possible cause Check Corrective action
Improper combination of indoor unit and
outdoor unit.
Check combination. Adjust installation when required.
Wiring abnormality between indoor unit
and outdoor unit.
Check wiring between indoor unit and out-
door unit.
Adjust wiring between indoor unit and out-
door unit when required.
Replace wiring between indoor unit and
outdoor unit when required.
Faulty outdoor unit main PCB. Check if the HAP LED is blinking in regu-
lar intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Restore the power to the outdoor main
PCB.
Replace outdoor main PCB when HAP
LED is not blinking in regular intervals.
Faulty indoor unit main PCB. Check if the HAP LED is blinking in regu-
lar intervals.
Check if the correct spare part is installed.
Check if the indoor main PCB receives
power.
Restore the power to the indoor main
PCB.
Replace indoor main PCB when HAP LED
is not blinking in regular intervals.
Check procedures Replacing procedures
"Main PCB" on page 53 "Replacing main PCB" on page 84
Trigger Effect Reset
When the interunit wiring between indoor
and outdoor unit is incorrect.
Piping abnormality.
Unit will stop operating. Automatic reset.
Possible cause Check Corrective action
Faulty wiring between indoor and outdoor
unit.
Check wiring between indoor and outdoor
unit.
Correct wiring.
Refrigerant shortage (incorrect
charge/leakage).
Check for refrigerant shortage.
Perform a leak test.
If required, repair the leak and charge the
correct amount of refrigerant.
Refrigerant circuit is clogged. Check for possible blockage (Blockages
can be checked by measuring the refriger-
ant/pipe temperature. Sudden drop in
temperature could indicate a blockage.
(Remark: This is not valid for the expan-
sion valve.)).
Check procedures Replacing procedures
"Wiring diagram" on page 98

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXM50M and is the answer not in the manual?

Daikin 2MXM50M Specifications

General IconGeneral
TypeAir conditioner outdoor unit
Multi-split-
Product colorWhite
Gas hose diameter9.5 mm
Drain hose diameter16 mm
Liquid hose diameter6.35 mm
Outdoor unit depth285 mm
Outdoor unit width765 mm
Outdoor unit height550 mm
Outdoor unit weight41000 g
Outdoor unit noise level486.35 dB
Outdoor unit package depth357 mm
Outdoor unit package width900 mm
Outdoor unit package height614 mm
Outdoor unit package weight43000 g
Outdoor unit sound power level62 dB
Current16 A
AC input voltage220 - 240 V
AC input frequency50 Hz

Related product manuals