10 | Configuration
Installer reference guide
220
EPRA08~12EAV3+W1 + ETVH12SU18+23EA6V
Daikin Altherma 3 H MT F
4P644482-1 – 2021.03
Mixing valve turning time
If a third party mixing valve is installed in combination with controller EKMIKPOA,
the valve turning time must be set accordingly.
For this setting, space heating/cooling and tank operation MUST be off:
[C.2] Space heating/cooling=0 (Off) and [C.3] Tank=0 (Off). See
"10.5.12Operation"[4220].
# Code Description
[9.P.5] [7-0C] Mixing valve turning time: Time in
seconds for the mixing valve to turn from one
side to the other.
20~300sec (default: 125)
10.5.10 Commissioning
Overview
The following items are listed in the submenu:
A
Commissioning
User profile
Installer settings
Information
Operation
[A] Commissioning
[A.1] Operation test run
[A.2] Actuator test run
[A.3] Air purge
[A.4] UFH screed dryout
About commissioning
See: "11Commissioning"[4226]
10.5.11 User profile
[B] User profile: See "To change the user permission level"[4135].
B
User profile
Operation
Commissioning
Installer settings
Malfunctioning
10.5.12 Operation
Overview
The following items are listed in the submenu:
C
Operation
Malfunctioning
User profile
Commissioning
Room
[C] Operation
[C.2] Space heating/cooling
[C.3] Tank
To enable or disable functionalities
In the operation menu, you can separately enable or disable functionalities of the
unit.

Table of Contents

Questions and Answers:

Daikin Altherma 3 H MT W Specifications

General IconGeneral
Energy efficiency class (Heating)A+++
Energy efficiency class (Cooling)A++
RefrigerantR-32
TypeAir to Water
Heating capacity4 - 16 kW
Operating range (heating)-25°C to 35°C
Weight (Outdoor Unit)85 kg

Related product manuals