Si12-411A Control Specification
Function and Control 95
3.6 Freeze-up Protection Control
Outline During cooling operation, the signals being sent from the indoor unit allow the operating
frequency limitation and then prevent freezing of the indoor heat exchanger. (The signal from
the indoor unit must be divided into the zones as the followings.
Detail Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec from
operation start and after 30 sec from changing number of operation room.
Control in Each Zone
3.7 Heating Peak-cut Control
Outline Heat Pump Only
During heating operation, the signals being sent form the indoor unit allow the operating
frequency limitation and prevent abnormal high pressure. (The signal from the indoor unit must
be divided as follows.)
Detail Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 min from
operation start and after A sec from changing number of operation room.
Control in Each Zone
The maximum value of heat exchange intermediate temperature of each indoor unit controls the
following (excluding stopped rooms).
A
30
2
When increase
When decrease

Table of Contents

Other manuals for Daikin CDKD60CVM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin CDKD60CVM and is the answer not in the manual?

Daikin CDKD60CVM Specifications

General IconGeneral
BrandDaikin
ModelCDKD60CVM
CategoryAir conditioning
LanguageEnglish

Related product manuals