Troubleshooting Si12-411A
198 Service Diagnosis
5.21 Radiation Fin Temperature Rise
Remote
Controller
Display
L4
Outdoor Unit LED
Display
A
5
1
1
2
1
3
1
4
4
Method of
Malfunction
Detection
A radiation fin temperature rise is detected by checking the radiation fin temperature being
detected by the fin thermistor with the compressor on.
Malfunction
Decision
Conditions
If the radiation fin temperature with the compressor on is above 90°C for 5.2~7.5 kW-or-smaller
class systems or above 85°C for 8.0 · 9.0 kW class systems,
If a radiation fin temperature rise takes place 4 times successively, the system will be shut
down.
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Supposed
Causes
Fin temperature rise due to defective outdoor unit fan
Fin temperature rise due to short-circuit
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective

Table of Contents

Other manuals for Daikin CDKD60CVM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin CDKD60CVM and is the answer not in the manual?

Daikin CDKD60CVM Specifications

General IconGeneral
BrandDaikin
ModelCDKD60CVM
CategoryAir conditioning
LanguageEnglish

Related product manuals