Si12-411A Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)
Removal Procedure 255
2.8 Removal of Solenoid Valve and Shunt
Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure Points
Before taking this
procedure, make sure
there is no refrigerant gas
left in the refrigerant
pipes.
Caution
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the gas
welding rod.
Warning
If refrigerant gas leaks during
the job, ventilate the room.
(Bear in mind that if the
refrigerant gas is exposed to
open flames, noxious gas may
be generated.)
Reassembling precautions
Wrap the solenoid valve body
with wet cloth. Splash water
over the cloth before it is dried
to prevent the valve from being
overheated.
1
Disconnect the 2
brazed points (a) and
(b) in this order.
2
Remove the putty of the
shunt.
3
Disconnect the 5
brazed points of the
shunt.

Table of Contents

Other manuals for Daikin CDKD60CVM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin CDKD60CVM and is the answer not in the manual?

Daikin CDKD60CVM Specifications

General IconGeneral
BrandDaikin
ModelCDKD60CVM
CategoryAir conditioning
LanguageEnglish

Related product manuals