Troubleshooting Si12-411A
194 Service Diagnosis
5.19 Thermistor or Related Abnormality (Outdoor Unit)
Remote
Controller
Display
P4, J3, J6, J8, J9, H9
Outdoor Unit LED
Display
A
5
1
4
2
4
3
1
4
1
Method of
Malfunction
Detection
This type of error is detected by checking the thermistor input voltage to the microcomputer.
[A thermistor error is detected by checking the temperature being detected by each thermistor.]
Malfunction
Decision
Conditions
When the thermistor input is above 4.96 V or below 0.04 V with the power on, the J3 error is
judged if the discharge pipe thermistor temperature is smaller than the condenser thermistor
temperature, or the system will be shut down if all the units are judged with the J8 error.
Supposed
Causes
Connector in poor contact
Thermistor defective
Outdoor unit PCB defective
Indoor unit PCB defective
Condenser thermistor defective in the case of J3 error (outdoor unit heat exchanger
thermistor in the cooling mode, or indoor unit heat exchanger thermistor in the heating
mode)

Table of Contents

Other manuals for Daikin CDKD60CVM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin CDKD60CVM and is the answer not in the manual?

Daikin CDKD60CVM Specifications

General IconGeneral
BrandDaikin
ModelCDKD60CVM
CategoryAir conditioning
LanguageEnglish

Related product manuals