SERVICING
77
S-314 CHECKING FLAME SENSOR
A flame sensing device is used in conjunction with the igni-
tion control module to prove combustion. If proof of flame is
not present the control will de-energize the gas valve and
"retry" for ignition or lockout.
WARNING
HIGH VOLTAGE
D
ISCONNECT ALL POWER BEFORE SERVICING OR
INSTALLING THIS UNIT.
MULTIPLE POWER SOURCES MAY
BE PRESENT.
FAILURE TO DO SO MAY CAUSE PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
1. Connect a micro-amp meter in series with this wire and
the sensor terminal.
L
INE VOLTAGE NOW PRESENT
WARNING
2. Place the unit into a heating cycle.
3. As soon as flame is established a micro-amp reading
should be evident once proof of flame (micro-amp read-
ing) is established, the hot surface ignitor will be de-
energized.
4. The Integrated Ignition controls will have 1 to 4 micro-
amps. If the micro-amp reading is less than the mini-
mum specified, check for high resistance wiring con-
nections, sensor to burner gap, dirty flame sensor, or
poor grounding.
5. If absolutely no reading, check for continuity on all com-
ponents and if good - replace ignition control module.
NOTE: Contaminated fuel or combustion air can create a
nearly invisible coating on the flame sensor. This coating
works as an insulator causing a loss in the flame sense
signal. If this situation occurs the flame sensor must be
cleaned with steel wool.