SiUS071735EB Main Functions
Functions and Control 20
1.4 Program Dry Operation
Outline Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and FAN setting buttons are inoperable.
Details The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two zones.
Then, the unit operates in an appropriate capacity for each zone to maintain the temperature and
humidity at a comfortable level.
Room thermistor
temperature at start-up
Target temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
24.5°C or more
(76.1°F or more)
Room thermistor
temperature at start-up
X – 2.5°C
(X – 4.5°F)
X – 1.0°C
(X – 1.8°F)
16.5 ~ 24°C
(61.7 ~ 75.2°F)
X – 2.0°C
(X – 3.6°F)
X – 1.0°C
(X – 1.8°F)
16°C or less
(60.8°F or less)
16°C
(60.8°F)
X – 2.0°C
(X – 3.6°F)
X – 1.0°C = 15°C
(X – 1.8°F = 59°F)
Zone A = Thermostat OFF
Target temperature X
Zone B
Room temperature Room temperature
Zone C = Thermostat ON
Y = X – 2.5°C (4.5°F)
or
Y = X – 2.0°C (3.6°F)
Z = X – 1.0°C (1.8°F)
X – 1.0°C (1.8°F)
(R24367)

Table of Contents

Other manuals for Daikin RX09RMVJU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RX09RMVJU and is the answer not in the manual?

Daikin RX09RMVJU Specifications

General IconGeneral
BrandDaikin
ModelRX09RMVJU
CategoryInverter
LanguageEnglish

Related product manuals