Troubleshooting SiUS071735EB
69 Service Diagnosis
4.5 Indoor Fan PCB Abnormality
Error Code A8
Method of Error
Detection
Microcomputer checks the voltage state of the fan PCB.
Error Decision
Conditions
Overvoltage or voltage drop is detected on the fan PCB.
Supposed
Causes
Defective fan PCB
External factor such as noise
Troubleshooting
Caution
Be sure to turn off the power switch before connecting
or disconnecting connectors, or parts may be damaged.
Check for the indoor unit control
PCB (A1P) and the fan PCB
(A2P).
Connect the connector correctly.
NO
YES
YES
Is the
connector X3A on
the fan PCB connected
correctly?
Connect the connector correctly.
NO
YES
Is the
connector X70A on
the indoor unit control PCB
connected correctly?
Replace the harness.
YES
Is the harness
connecting X3A and X70A
broken?
NO
NO
Remove the external factor.
YES
Is there any external
factor such as noise?
Normal.
NO
Error is displayed
again.
Turn OFF the power supply
and then turn it ON again.
Start operation with the
remote controller.
(R25085)

Table of Contents

Other manuals for Daikin RX09RMVJU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RX09RMVJU and is the answer not in the manual?

Daikin RX09RMVJU Specifications

General IconGeneral
BrandDaikin
ModelRX09RMVJU
CategoryInverter
LanguageEnglish

Related product manuals