EasyManuals Logo
Home>Daikin>Air Conditioner>Super Multi NX B series

Daikin Super Multi NX B series User Manual

Daikin Super Multi NX B series
302 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #198 background imageLoading...
Page #198 background image
Si12-308 Troubleshooting
Service Diagnosis 187
5.14 Input Over Current Detection
Remote
Controller
Display
E8
Outdoor Unit LED
Display
A
5
1
1
2
4
3
1
4
4
Method of
Malfunction
Detection
An input over-current is detected by checking the input current value being detected by CT with
the compressor running.
Malfunction
Decision
Conditions
The following CT input with the compressor running continues for 2.5 seconds.
CT input : Above 20 A
The system will be shut down if the error occurs 16 times.
Clearing condition : Continuous run for about 5 minutes (normal)
Supposed
Causes
Over-current due to compressor failure
Over-current due to defective power transistor
Over-current due to defective inverter main circuit electrolytic capacitor
Over-current due to defective outdoor unit PCB
Error detection due to outdoor unit PCB
Over-current due to short-circuit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi NX B series and is the answer not in the manual?

Daikin Super Multi NX B series Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi NX B series
CategoryAir Conditioner
LanguageEnglish

Related product manuals