SiBE121021_C Troubleshooting for RA Indoor Unit - F(C)TXG, FTXS, ATXS, FVXS, FLK(X)S, FDK(X)S Series
Service Diagnosis 309
5.2 Freeze-up Protection Control or Heating Peak-cut
Control
Remote
Controller
Display
A5
Method of
Malfunction
Detection
îš„
Freeze-up protection control
During cooling operation, the freeze-up protection control (operation halt) is activated
according to the temperature detected by the indoor heat exchanger thermistor.
îš„
Heating peak-cut control
During heating operation, the temperature detected by the indoor heat exchanger thermistor
is used for the heating peak-cut control (operation halt, outdoor fan stop, etc.)
Malfunction
Decision
Conditions
îš„
Freeze-up protection control
During cooling operation, the indoor heat exchanger temperature is below 0°C.
îš„
Heating peak-cut control
During heating operation, the temperature detected by the indoor heat exchanger thermistor
is above 65°C.
Supposed
Causes
îš„
Clogged air filter of the indoor unit
îš„
Dust accumulation on the indoor heat exchanger
îš„
Short-circuited air
îš„
Defective indoor heat exchanger thermistor
îš„
Defective indoor unit PCB