AK-CC 550A Manual RS8FS402 © Danfoss 2016-03 15
Survey of functions
Function Para-
meter
Parameter by operation via data
communication
Normal display
Normally the temperature value from one of the two thermostat sensors S3 or S4 or a
mixture of the two measurements is displayed.
In o17 the ratio is determined.
Display air (u56)
Thermostat Thermostat control
Set point
Regulation is based on the set value plus a displacement, if applicable. The value is set
via a push on the centre button.
The set value can be locked or limited to a range with the settings in r02 and r 03.
The reference at any time can be seen in "u91 Cutout temp".
Cutout °C
Dierential
When the temperature is higher than the reference + the set dierential, the com-
pressor relay will be cut in. It will cut out again when the temperature comes down to
the set reference.
r01 Dierential
Setpoint limitation
The controller’s setting range for the setpoint may be narrowed down, so that much
too high or much too low values are not set accidentally - with resulting damages.
To avoid a too high setting of the setpoint, the max. allowable reference value may be
lowered.
r02 Max cutout °C
To avoid a too low setting of the setpoint, the min. allowable reference value may be
increased.
r03 Min cutout °C
Correction of the display’s temperature
If the temperature at the products and the temperature received by the controller are
not identical, an oset adjustment of the display temperature can be carried out.
r04 Disp. Adj. K
Temperature unit
Set here if the controller is to show temperature values in °C or in °F.
r05 Temp. unit
°C=0. / °F=1
(Only °C on AKM, whatever the set-
ting)
Correction of signal from S4
Compensation possibility due to long sensor cable
r09 Adjust S4
Correction of signal from S3
Compensation possibility due to long sensor cable
r10 Adjust S3
Start / stop of refrigeration
With this setting refrigeration can be started, stopped or a manual override of the
outputs can be allowed. (For manual control the value is set at -1. Then the AKV outlet
and the relay outlets can be force-controlled by the respective reading parameters
(u23, u58, etc.). Here the read value can be overwritten.)
Start / stop of refrigeration can also be accomplished with the external switch func-
tion connected to a DI input.
Stopped refrigeration will give a ”Standby alarm.
r12 Main Switch
1: Start
0: Stop
-1: Manual control of outputs allowed
Night setback value
The thermostat’s reference will be the setpoint plus this value when the controller
changes over to night operation. (Select a negative value if there is to be cold ac-
cumulation.)
r13 Night oset
Thermostat function
Here it is dened how the thermostat is to operate. Either as an ordinary ON/OFF ther-
mostat or as a modulating thermostat.
1: ON/OFF thermostat
2: Modulating
When operation is ”modulating” the AKV valve will limit the ow of refrigerant so that
the temperature variation will be less than for the ON/OFF thermostat.
The dierential (r01) must not be set lower than 2K for "modulating".
In a decentralised plant you must select the ON/OFF thermostat setting.
r14 Therm. mode
Selection of thermostat sensor
Here you dene the sensor the thermostat is to use for its control function. S3, S4, or a
combination of them. With the setting 0%, only S3 is used (Sin). With 100%, only S4.
r15 Ther. S4 %
Ref. Dif.

Other manuals for Danfoss AK-CC 550A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-CC 550A and is the answer not in the manual?

Danfoss AK-CC 550A Specifications

General IconGeneral
BrandDanfoss
ModelAK-CC 550A
CategoryController
LanguageEnglish

Related product manuals