Instructions ECL Comfort 210 / 310, communication description
Table 6-13:
Sensor S13 S14 S15 S16 S17 S18
PNU
4126 4127 4128 4129 4130 4131
Option: 0 = None
Option: 1 = Pull up
Option: 2 = Cap load
Option: 3 = Pull up & Cap load
Option: 255 = Default
A write error will be returned if the application does not allow
the input configuration to be changed.
6.16 Unit and pulse
The unit setting (PNU 1X115) is a special setting which
depends on the value of the pulse setting (PNU 1X114). See
in the table below what the unit value means depending on
the pulse value.
Pulse = 0 Pulse > 0
Unit = 0 L/h mL, L/h
Unit = 1 L/h L, L/h
Unit = 2 m3/h mL, m3/h
Unit = 3 m3/h L, m3/h
Unit = 4 kW Wh, kW
Unit = 5 kW kWh, kW
Unit = 6 MW kWh, MW
Unit = 7 MW MWh, MW
Unit = 8 GW MWh, GW
Unit = 9 GW GWh, GW
Danfoss District Energy VI.LG.V3.02 DEN-SMT/DK