Instructions ECL Comfort 210 / 310, communication description
9.3 Energy meter type descriptions
The following shows the possible types and the related values. Note that some energy meter only support a limited number of
parameters.
The type 0 & 1 values should be supported by most energy meters.
"PNU offset" Type 0 Type 1
0
Address Address
1
Type Type
2
Scan time Scan time
3
ID / Serial ID / Serial
4
- low part - low part
5
Reserved Reserved
6 Flow temp. [0,01 °C] Flow temp. [0,01 °C]
7 Return temp. [0,01 °C] Return temp. [0,01 °C]
8 Flow [0,1 l/h] Flow [0,1 l/h]
9 - low - low
10 Power [0,1 kW] Power [0,1 kW]
11 - low - low
12 Acc. Volume [0,1 m3] Acc. Volume [0,1 m3]
13 - low - low
14 Acc. Energy [0,1 kWh] Acc. Energy [0,1 MWh]
15 - low - low
16
17
18
19
20
21
22
23
24
Danfoss District Energy VI.LG.V3.02 DEN-SMT/DK