Copy from the programming key
This function downloads a set of settings earlier saved in the controller. Select the
relevant number.
All settings except for Application (o61) and Address (o03) will be copied. When copy-
ing has started the display returns to o66. After two seconds you can move back into
the menu again and check whether the copying was satisfactory. Showing of a nega-
tive gure spells problems. See the signicance in the Fault Message section.
o66 -
Save as factory setting
With this setting you save the controller’s actual settings as a new basic setting (the
earlier factory settings are overwritten).
o67 -
- - - Night Setback
0=Day
1=Night
Service Service
Temperature measured with S5 sensor u09 S5 temp.
Status on DI1 input. on/1=closed u10 DI1 status
Temperature measured with S3 sensor
u12 S3 air temp
Status on night operation (on or o) 1=closed
u13 Night Cond.
Temperature measured with S4 sensor u16 S4 air temp
Thermostat temperature u17 Ther. air
Read the present regulation reference u28 Temp. ref.
Status on DI2 output. on/1=closed u37 DI2 status
Temperature shown on display
u56 Display air
Measured temperature for alarm thermostat u57 Alarm air
* Status on relay for cooling u58 Comp1/LLSV
* Status on relay for fan u59 Fan relay
* Status on relay for defrost u60 Def. relay
* Status on relay for railheat
u61 Railh. relay
* Status on relay for alarm u62 Alarm relay
* Status on relay for light u63 Light relay
*) Not all items will be shown. Only the function belonging to the selected applica-
tion is shown.