Fault message Alarms
In an error situation the LED’s on the front will ash and the alarm relay will be acti-
vated. If you push the top button in this situation you can see the alarm report in the
display. If there is more than one, simply push the button to scroll through and view
them.
There are two kinds of error reports - it can either be an alarm occurring during the
daily operation, or there may be a defect in the installation.
A-alarms will not become visible until the set time delay has expired.
E-alarms, on the other hand, will become visible the moment the error occurs.
(An A alarm will not be visible as long as there is an active E alarm).
Here are the messages that may appear: 1 = alarm
A1: High temperature alarm High t. alarm
A2: Low temperature alarm Low t. alarm
A4: Door alarm Door Alarm
A5: Information. Parameter o16 is expired Max Hold Time
A15: Alarm. Signal from DI1 input DI1 alarm
A16: Alarm. Signal from DI2 input DI2 alarm
A45: Standby position (stopped refrigeration via r12 or DI input) Standby mode
A59: Case cleaning. Signal from DI1 or DI2 input Case cleaning
Max. def time
E1: Faults in the controller EKC error
E6: Fault in real-time clock. Check the battery / reset the clock. -
E25: Sensor error on S3 S3 error
E26: Sensor error on S4 S4 error
E27: Sensor error on S5 S5 error
When copying settings to or from a copying key with functions o65 or o66, the fol-
lowing information may appear:
0: Copying concluded and OK
4: Copying key not correctly mounted
5: Copying was not correct. Repeat copying
6: Copying to EKC incorrect. Repeat copying
7: Copying to copying key incorrect. Repeat copying
8: Copying not possible. Order number or SW version do not match
9: Communication error and timeout
10: Copying still going on
(The information can be found in o65 or o66 a couple of seconds after copying has
been started).
Alarm destinations
The importance of the individual
alarms can be dened with a setting
(0, 1, 2 or 3)