2 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 EKC 347
Introduction
LED's on front panel
Opening signal to valve
Indication of upper level limit
Indication of lower level limit
Indication of alarm level
Application
The controller is used for regulation of the refrigerant level in:
• Pump reservoirs
• Separators
• Intermediate coolers
• Economisers
• Condensers
• Receivers
Functions
• Liquid level control
• Alarm if the set alarm limits are exceeded
• Relay outputs for upper and lower level limits and for alarm level
• Analog input signal which can displace the reference
• PI control
• Low or High side control
When AKV/A is selected, a MASTER/SLAVE system can run up to 3
AKV/A with distributed Opening Degree
• Manual control of output
• Limitation of Opening degree possible
• ON/OFF operation with hysteresis
Extra options
• PC operation
The controller can be provided with data communication, so
that it may be hooked up with other products in the ADAP-
KOOL® range of refrigeration controls. Operation, moni toring
and data collection can then be performed from a PC - either in
situ or at a service company.
System
A signal transmitter will constantly measure the refrigerant liquid
level in the reservoir - the controller will receive the signal and
subsequently control the valve, in order to control the refrigerant
liquid level according to liquid level setpoint.
Signaltransmitter
With the capacitive rod it is possible to set the refrigerant level
within a wide range.
EKC 347
The controller receive a signal and are then able to contol
low or high side applications. A analog input signal (voltage/
current) can displace the setpoint and then remote change of
setpoint is thus possible.
EKC 347 does support 2 types of Danfoss expansion valves. (see
below)
One analog input is available as feed back from ICM in order to
indicate Opening degreee of the ICM.
Expansions valve
Two types of Danfoss expansion valves can be used
ICM - ICM are direct operated motorized valves driven by
digital stepper motor type ICAD
AKV/A - AKVA or AKV are pulse-width modulating expansion
valves.
EKC 347
All

Other manuals for Danfoss EKC 347

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKC 347 and is the answer not in the manual?

Danfoss EKC 347 Specifications

General IconGeneral
BrandDanfoss
ModelEKC 347
CategoryController
LanguageEnglish

Related product manuals