Miscellaneous Miscellaneous
Valve and output signal
The controller can control three types of expansion valves - ICM or AKV/A.
With AKV/A up to three EKC 347 controllers can be linked up to a MASTER/SLAVE
function (this function is only used if there is a need for several parallel AKV/A expan-
sion valves). The application is selected with one of the following settings:
1: ICM. AO: 4-20 mA
2: ICM. AO: 0-20 mA
3: AKV/A, AO: 4-20 mA
4: AKV/A, AO: 0-20 mA
or, if the master/slave function is used::
5: AKV/A, MASTER
6: AKV/A, SLAVE 1/1. AO:4-20 mA
7: AKV/A, SLAVE 1/1. AO:0-20 mA
8: AKV/A, SLAVE 1/2. AO:4-20 mA
9: AKV/A, SLAVE 1/2. AO:0-20 mA
10: AKV/A, SLAVE 2/2. AO:4-20 mA
11: AKV/A, SLAVE 2/2. AO:0-20 mA
12: AKV/A, SLAVE 1/1. AO:4-20 mA - AO always updated
13: AKV/A, SLAVE 1/1. AO:0-20 mA- AO always updated
14: AKV/A, SLAVE 1/2. AO:4-20 mA- AO always updated
15: AKV/A, SLAVE 1/2. AO:0-20 mA- AO always updated
16: AKV/A, SLAVE 2/2. AO:4-20 mA- AO always updated
17: AKV/A, SLAVE 2/2. AO:0-20 mA- AO always updated
With settings 1 and 2 the AO [mA] signal is dedicated for the motor valve ICM.
With settings 3, 4, AO [mA] will be send out a signal for process indications.
With settings 6, 7, 8, 9, 10 or 11, AO [mA] on EKC 347 SLAVE, will be send out a signal
for process indications.
With settings 12, 13, 14, 15, 16 or 17, AO will also be updated (active) when DI is OFF
o09
o09 AO type
Reference displacement
If you wish to connect a signal that is to displace the controllers control reference, the
signal must be dened in this menu.
The signal is connected to terminals 19-21 or 20-21
0: No signal
1: 4 - 20 mA
2: 0 - 20 mA
3: 2 - 10 V
4: 0 - 10 V
(The min. value will give no displacement. The max. value will displace the reference
with the value set in menu r06).
o10 o10 AI type
Input signal from the level-measuring unit
The input signal for terminals 14-16 or 15-16 must be dened:
0: No signal
1: Current signal of 4-20 mA
2: Voltage signal. The voltage range must be set in the next two menus. (If the con-
nections are a master/slave system and the signal to the master is 4 to 20 mA, the
setting in the slave modules must also be selected to 1 – this must be done, even if
the signal is connected to the voltage input).
o31 o31 Levelsign.
Voltage signal’s lower value
(only if the setting in 031 = 2).
o32 o32 Lev. V. Low
Voltage signal’s upper value
(only if the setting in o31 = 2)
o33 o33 Lev. V. High
Position signal
If a ICM valve is selected it is possible to have ICM valve position as a [mA] feed back
signal
0: Not used
1: ICM mA feedback signal from connected ICAD.
2: Not used
o34 o34 Valve feedb.
Frequency
Set the net frequency.
o12 o12 50 / 60 Hz
(50=0, 60=1)
Address
If the controller is built into a network with data communication, it must have an
address, and the master gateway of the data communication must then know this
address.
These settings can only be made when a data communication module has been
mounted in the controller and the installation of the data communication cable has
been completed.
This installation is mentioned in a separate document “RC8AC..
Following installation of a data com-
munication module, the controller can
be operated on a par with the other
controllers in ADAP-KOOL® refrigera-
tion controls.
The address is set between 1 and 60 o03 -
The address is sent to the gateway when the menu is set in pos. ON
(The setting will automatically change back to O after a few seconds.)
o04 -