EKC 347 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 9
Ordering
Type Function Code No.
EKC 347 Liquid level controller 084B7067
EKA 174
Data communication module
(accessories), (RS 485 module)
with galvanic separation
084B7124
Level transmitter/controller: .............Kindly refer to catalogue RK0YG
AKV / AKVA Valves: ................................Kindly refer to catalogue RK0YG
ICM and ICAD................ ..........................Kindly refer to DKRCI.PD.HT0.A
*) This setting will only be possible if a data communication module has been
installed in the controller.
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you recon nect the supply voltage
Error messages
The controller can give the following messages:
E1
Error message
Errors in the controller
E12
The external reference contribution is outside
the range
E21 Level signal outside the range 1)
E22 Signal from ICM/ICAD outside the range
A1
Alarm message
Upper level limit reached
A2 Lower level limit reached
A3 Alarm level limit reached
Dene the input signal on terminals 19, 20, 21 (external
reference displacement)
0: OFF
1: 4-20 mA
2: 0-20 mA
3: 2-10 V
4: 0-10 V
o10 0 4 0
Language
0=English, 1=German, 2=Frensh, 3=Danish, 4=Spanish,
5=Italian, 6=Swedish. When you change the setting
you must also activate o04.
o11* 0 6 0
Set supply voltage frequency o12
0/50
Hz
1/60
Hz
0
Selection of parameter for display and AO (except from
when o09=1,2 or 5)
If o34 = 0:
0: Liquid level is show
1: Valves opening degree OD will be shown
If o34 = 1:
0: Liquid level is show
1: The ICM valve position feed back signal [%] will be
shown
o17 0 1 0
Manual control of outputs:
OFF: No manual control
1: Upper level relay put in pos. ON
2: Lower level relay put in pos. ON
3: AKV/A output put in pos. ON
4: Alarm relay activated (cut out)
o18 OFF 4 0
Dene input signal (level signal) on terminals 14, 15, 16
0: OFF
1: 4-20 mA
2: 0-10 V (also set the voltage values in the next two
menus)
Read functional description if the connection used is a
master/slave function.
o31 0 2 1
Dene input signal’s lower value for terminal 14, if
required
o32 0.0 V 4.9 V 4.0
Dene input signal’s upper value for terminal 14, if
required
o33 5.0 V 10 V 6.0
Dene input signal on terminals 17-18
0: Not used
1: ICM mA feedback signal from ICAD connected
2: Not used
o34 0 2 0
Service
Read liquid level u01 %
Read liquid level reference u02 %
Read external contribution to the reference u06 mA
Read external contribution to the reference u07 V
Read current signal on the analog output u08 mA
Read status of input DI u10
Read valve’s opening degree u24 %
Read level signal u30 mA
Read level signal u31 V
Read signal from ICM/ICAD u32 mA
Read signal from ICM/ICAD converted into % u33 %
Continued from previous page
1)
If E21 is detected. EKC 347 will force the valve to close or open the valve depending
af n35
If Low pressure has been selected. (n35=0)
The valve is forced to fully closed, however if Min. Opening Degree (n33) is higher
than 0 the valve will open to the value of n33
If High pressure has been selected. (n35=1)
The valve is forced to fully open, however if Max. Opening Degree (n32) is lower than
100 the valve will open to the value of n32

Other manuals for Danfoss EKC 347