4 Control
4.1 I/O Assembly Instances
I/O assembly instances are some dened process control objects with dened content comprising control and status
information.
Unlike DeviceNet, it is possible to run with asymmetrical instances. For example, 101/153 = 8 bytes/20 bytes.
It is not possible to mix instances across proles, for example 20/100. Assembly instances must be consistent to the ODVA
or frequency converter prole.
Read the controlling instance in chapter 5.2.3 12-2* Process Data.
Prole
(parameter 8-10 Contr
ol Word Prole)
Direction
Instances
(decimal)
Size
(bytes)
Data
ODVA
Originator⇒Target
20 4
21 4
Target⇒Originator
70 4
71 4
Frequency converter
Originator⇒Target
100 4
101 8
103 20
Target⇒Originator
150 4
151 8
153 20
Table 4.1 I/O Assembly Instance Options for Controlling and Monitoring the Frequency Converter
NOTICE
Use of 32-bit process data.
To congure a 2-word (32-bit) parameter read/write, use 2 consecutive arrays in parameter 12-21 Process Data Cong
Write and parameter 12-22 Process Data Cong Read, like [2]+[3], [4]+[5], [6]+[7], and so on. Read/write of 2-word values
in arrays like [3]+[4], [5]+[6], [7]+[8] is not possible.
Control EtherNet/IP
12 Danfoss A/S © 06/2016 All rights reserved. MG07H102
44