Frequency converter P18K P22K P30K P37K P45K P55K P75K P90K
Typical shaft output [kW] 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0
Typical shaft output [HP] 25.0 30.0 40.0 50.0 60.0 70.0 100.0 125.0
IP20 frame H5 H5 H6 H6 H6 H7 H7 H8
Maximum cable size in terminals
(mains, motor) [mm
2
(AWG)]
16 (6) 16 (6) 35 (2) 35 (2) 35 (2) 50 (1) 95 (0) 120
(250MCM)
Output current - 40 °C (104 °F) ambient temperature
Continuous (3x380–440 V)[A] 37.0 42.5 61.0 73.0 90.0 106.0 147.0 177.0
Intermittent (3x380–440 V) [A] 40.7 46.8 67.1 80.3 99.0 116.0 161.0 194.0
Continuous (3x440–480 V) [A] 34.0 40.0 52.0 65.0 80.0 105.0 130.0 160.0
Intermittent (3x440–480 V) [A] 37.4 44.0 57.2 71.5 88.0 115.0 143.0 176.0
Maximum input current
Continuous (3x380–440 V) [A] 35.2 41.5 57.0 70.0 84.0 103.0 140.0 166.0
Intermittent (3x380–440 V) [A] 38.7 45.7 62.7 77.0 92.4 113.0 154.0 182.0
Continuous (3x440–480 V) [A] 29.3 34.6 49.2 60.6 72.5 88.6 120.9 142.7
Intermittent (3x440–480 V) [A] 32.2 38.1 54.1 66.7 79.8 97.5 132.9 157.0
Maximum mains fuses
Estimated power loss [W],
best case/typical
1)
412/456 475/523 733 922 1067 1133 1733 2141
Weight enclosure IP20 [kg (lb)] 9.5 (20.9) 9.5 (20.9) 24.5 (54) 24.5 (54) 24.5 (54) 36.0 (79.4) 36.0 (79.4) 51.0
(112.4)
Efficiency [%], best case/typical
2)
98.1/97.9 98.1/97.9 97.8 97.7 98 98.2 97.8 97.9
Output current - 50 °C (122 °F) ambient temperature
Continuous (3x380–440 V) [A] 34.1 38.0 48.8 58.4 72.0 74.2 102.9 123.9
Intermittent (3x380–440 V) [A] 37.5 41.8 53.7 64.2 79.2 81.6 113.2 136.3
Continuous (3x440–480 V) [A] 31.3 35.0 41.6 52.0 64.0 73.5 91.0 112.0
Intermittent (3x440–480 V) [A] 34.4 38.5 45.8 57.2 70.4 80.9 100.1 123.2
Table 6.3 3x380–480 V AC, 18.5–90 kW (25–125 HP), Enclosure Type H5–H8
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may
increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to
www.danfoss.com/vltenergyefficiency.
2) Efficiency measured at nominal current. For energy efficiency class, see chapter 6.4.13 Ambient Conditions. For part load losses, see
www.danfoss.com/vltenergyefficiency.
Specifications Quick Guide
44 Danfoss A/S © 08/2014 All rights reserved. MG18A602
66

Other manuals for Danfoss FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 101 and is the answer not in the manual?

Danfoss FC 101 Specifications

General IconGeneral
BrandDanfoss
ModelFC 101
CategoryMedia Converter
LanguageEnglish

Related product manuals