6.4.13 Ambient Conditions
Enclosure IP20, IP54
Enclosure kit available IP21, TYPE 1
Vibration test 1.0 g
Maximum relative humidity 5%-95% (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60721-3-3), coated (standard) frame H1–H5 Class 3C3
Aggressive environment (IEC 60721-3-3), non-coated frame H6–H10 Class 3C2
Aggressive environment (IEC 60721-3-3), coated (optional) frame H6–H10 Class 3C3
Aggressive environment (IEC 60721-3-3), non-coated frame I2–I8 Class 3C2
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
1)
See maximum output current at 40/50 °C in chapter 6.1.2 3x380–480 V AC
Minimum ambient temperature during full-scale operation 0 °C
Minimum ambient temperature at reduced performance -20 °C
Minimum ambient temperature at reduced performance -10 °C
Temperature during storage/transport -30 to +65/70 °C
Maximum altitude above sea level without derating 1000 m
Maximum altitude above sea level with derating 3000 m
Derating for high altitude, see chapter 6.3.2 Derating for Low Air Pressure and High Altitudes
Safety standards EN/IEC 61800-5-1, UL 508C
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-3-12, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN 61000-4-6
Energy efficiency class IE2
1) Refer to special conditions in the design guide for:
•
Derating for high ambient temperature
•
Derating for high altitude
2) Determined according to EN50598-2 at:
•
Rated load
•
90% rated frequency
•
Switching frequency factory setting
•
Switching pattern factory setting
Specifications Quick Guide
MG18A602 Danfoss A/S © 08/2014 All rights reserved. 53