6.1.2 3x380–480 V AC
Frequency converter PK37 PK75 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5 P11K P15K
Typical shaft output [kW] 0.37 0.75 1.5 2.2 3.0 4.0 5.5 7.5 11.0 15.0
Typical shaft output [HP] 0.5 1.0 2.0 3.0 4.0 5.0 7.5 10.0 15.0 20.0
IP20 frame H1 H1 H1 H2 H2 H2 H3 H3 H4 H4
Maximum cable size in
terminals (mains, motor) [mm
2
(AWG)]
4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 16 (6) 16 (6)
Output current - 40 °C (104 °F) ambient temperature
Continuous (3x380–440 V)[A] 1.2 2.2 3.7 5.3 7.2 9.0 12.0 15.5 23.0 31.0
Intermittent (3x380–440 V) [A] 1.3 2.4 4.1 5.8 7.9 9.9 13.2 17.1 25.3 34.0
Continuous (3x441–480 V) [A] 1.1 2.1 3.4 4.8 6.3 8.2 11.0 14.0 21.0 27.0
Intermittent (3x441–480 V) [A] 1.2 2.3 3.7 5.3 6.9 9.0 12.1 15.4 23.1 29.7
Maximum input current
Continuous (3x380–440 V) [A] 1.2 2.1 3.5 4.7 6.3 8.3 11.2 15.1 22.1 29.9
Intermittent (3x380–440 V) [A] 1.3 2.3 3.9 5.2 6.9 9.1 12.3 16.6 24.3 32.9
Continuous (3x441–480 V) [A] 1.0 1.8 2.9 3.9 5.3 6.8 9.4 12.6 18.4 24.7
Intermittent (3x441–480 V) [A] 1.1 2.0 3.2 4.3 5.8 7.5 10.3 13.9 20.2 27.2
Maximum mains fuses
See chapter 3.2.4 Fuses and Circuit Breakers
Estimated power loss [W],
best case/typical
1)
13/15 16/21 46/57 46/58 66/83 95/118 104/131 159/198 248/274 353/379
Weight enclosure IP20 [kg (lb)] 2.0 (4.4) 2.0 (4.4) 2.1 (4.6) 3.3 (7.3) 3.3 (7.3) 3.4 (7.5) 4.3 (9.5) 4.5 (9.9) 7.9
(17.4)
7.9
(17.4)
Efficiency [%],
best case/typical
2)
97.8/97.3 98.0/97.6 97.7/97.2 98.3/97.9 98.2/97.8 98.0/97.6 98.4/98.0 98.2/97.8 98.1/97.
9
98.0/97.
8
Output current - 50 °C (122 °F) ambient temperature
Continuous (3x380–440 V) [A] 1.04 1.93 3.7 4.85 6.3 8.4 10.9 14.0 20.9 28.0
Intermittent (3x380–440 V) [A] 1.1 2.1 4.07 5.4 6.9 9.2 12.0 15.4 23.0 30.8
Continuous (3x441–480 V) [A] 1.0 1.8 3.4 4.4 5.5 7.5 10.0 12.6 19.1 24.0
Intermittent (3x441–480 V) [A] 1.1 2.0 3.7 4.8 6.1 8.3 11.0 13.9 21.0 26.4
Table 6.2 3x380–480 V AC, 0.37–15 kW (0.5–20 HP), Enclosure Type H1–H4
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may
increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to
www.danfoss.com/vltenergyefficiency.
2) Efficiency measured at nominal current. For energy efficiency class, see chapter 6.4.13 Ambient Conditions. For part load losses, see
www.danfoss.com/vltenergyefficiency.
Specifications Quick Guide
MG18A602 Danfoss A/S © 08/2014 All rights reserved. 43
6 6

Other manuals for Danfoss FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 101 and is the answer not in the manual?

Danfoss FC 101 Specifications

General IconGeneral
BrandDanfoss
ModelFC 101
CategoryMedia Converter
LanguageEnglish

Related product manuals