Quick Start Guide | ICM/ICAD Motorized Valves - Installation, Programming, and Troubleshooting
© Danfoss | DCS (MWA) | 2016.07
DKRCI.EI.HT0.B3.22 | 520H4763 | 13
Description
ICAD
parameter
Min Max
Factory
Setting
Stored Unit
Pass
word
Comments
In ON/OFF Mode
Closing speed
¡14 0 100 50/ 100
- No See ¡04.
If ¡26= 1 - 3 then factory settin qg = 100
If ¡26= 4 - 9 then factory setting = 50
Manual set point ¡15 0 100 0 No When ¡01= 2, ¡15 determine the start up value.
Encoder operation ¡16 0 1 1
Yes NB: Password protected. Password = 7
0: Encoder disabled. Means ICAD operation as ICAD 600A/ICAD 600A-TS/1200A without
encoder
1: Encoder enabled
Forced closing when
ICM valve Opening
Degree < 3%
i17 0 1 0
- No Enable/Disable forced closing
0: When ICM valve Opening Degree < 3% it will be forced to close regardless of
requested ICM valve Opening Degree
1: When ICM valve Opening Degree < 3% no forced to closing will take place
ICM conguration ¡26 0 9 0
Yes NB: Password protected. Password = 11
0: No valve selected. Alarm A1 will become active.
1: ICM 20 with ICAD 600A / ICMTS 20 with ICAD 600A-TS
2: ICM 25 with ICAD 600A
3: ICM 32 with ICAD 600A
4: ICM 40 with ICAD 1200A
5: ICM 50 with ICAD 1200A
6: ICM 65 with ICAD 1200A
7: ICM 100 with ICAD 1200A
8: ICM 125 with ICAD 1200A
9: ICM 150 with ICAD 1200A
Parameter list
(continued)
It is possible to restore the original factory settings to the ICAD by the following procedure:
1. Remove the power supply.
2. Activate the up arrow and the down arrow push buttons at the same time.
3. While pushing the up and down arrows, reconnect the power supply.
4. Release the up and down arrows.
5. When the display on the ICAD is alternating between CA and AI, the factory parameters have been restored.
Pre-startup Checklist
Valve Assembly
- Bonnet bolts are secure
- Seat has been replaced in body (ICM 20)
- The degree of opening of the valve is 75% or less
- Grease has been applied to o-ring area on valve stem
- Set screws have been uniformly tightened on ICAD Actuator
Power has been connected to actuator ( 24 V d.c.)
Back up power (UPS) has been connected to actuator (optional)
Control Wiring has been connected
- Signal input: digital or analog
- Feedback wiring (optional)
Programming (mandatory parameters)
- The mode of operation has been set (¡02)
- The input signal type has been set (¡03)
- The ICM valve size has been set (¡26)
Battery back-up (optional) parameters have been established (¡07, ¡08, ¡12)

Other manuals for Danfoss ICAD 600A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ICAD 600A and is the answer not in the manual?

Danfoss ICAD 600A Specifications

General IconGeneral
BrandDanfoss
ModelICAD 600A
CategoryController
LanguageEnglish