Quick Start Guide | ICM/ICAD Motorized Valves - Installation, Programming, and Troubleshooting
© Danfoss | DCS (MWA) | 2016.07
DKRCI.EI.HT0.B3.22 | 520H4763 | 4
Dierences between 1
st
and
2
nd
generation ICAD motor
actuators
The 2
nd
generation ICAD was released in the
beginning of 2010. The part numbers on the
label for the 2
nd
generation start with 027H9…
and the 1
st
generation part numbers started with
027H12… The cables of the 1
st
generation were
mounted through cable glands located in the
plastic top whereas the 2
nd
generation has the
cables mounted on connectors located in the
aluminum body.
Note: The wire colors are dierent between the two
generations and the following is a table with the
dierences and pictures of old and new generation.
1
st
Generation ICAD 2
nd
Generation ICAD
Power cable
(3-wire)
+ 19-24 V d.c. fail safe supply White (+) Black (+)
+ 24 V d.c. Brown (+) White (+)
- 24 C d.c. (GND) Green (-) Brown (-)
Communication
cable (7-wire)
Digital output (common alarm) White (-) Black (-)
Digital output (ICM fully open) Brown (-) Brown (-)
Digital output (ICM fully closed) Green (-) Red (-)
GND - ground Yellow (-) Orange (-)
Analog input (0/4-20 mA Grey (+) Yellow (+)
Analog input 0/2-10 V /
Digital ON/OFF input
Pink (+) Green (+)
Analog output 0/4-20 mA Blue (+) Blue (+)